SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
WUME-SCHG1IQRFB-1
15/184
Error code
■ List of error codes
Error code
(hexadecimal)
Description
Meaning
100
Station No. (i_uStationNo) is outside the
valid range
Set the Station No. (i_uStationNo) to a value from 1 to
64.
101
The information derived from the input
Start I/O No.(i_uStartIONo) and the
Station No. (i_uStationNo) is not
SC-HG1-C or SC-HG1-CEF.
Check if the Start I/O No.(i_uStartIONo) and the
Station No. (i_uStationNo) settings correctly indicate
the target communication unit.
102
CC-Link IE Field Flag (i_bIeFieldFlag) is
ON and Execution Command (i_bEN) is
ON
Turn ON Execution Command (i_bEN) with CC-Link
IE Field Flag (i_bIeFieldFlag) OFF.
200
Remote READY flag OFF
Check whether or not an error has occurred in the
communication unit. Check if the Start I/O
No.(i_uStartIONo) and the Station No. (i_uStationNo)
settings correctly indicate the target communication
unit.
201
Execution Command (i_bEN) turned OFF
before normal or error completion
Check that Normal Completion (o_bOK) or Error
Completion (o_bErr) has turned ON and then turn
OFF Execution Command (i_bEN). This error code is
output also when Execution Command (i_bEN) is
intentionally turned OFF before completion.
202
Execution Command (i_bEN) was turned
from ON to OFF and then turned from
OFF to ON while Execution Status
(o_bENO) was ON
Check that Execution Status (o_bENO) turned OFF
and then turn ON Execution Command (i_bEN).