№
SR-ZSV00039
-
55
-
Motor Business Unit, Appliances Company, Panasonic Corporation
6
-
4
-
3
Emergency Stop at Alarm
If an alarm occurs that requires an immediate stop, setting the following parameters will control the motor to
immediately stop it.
(1) Related parameters
Category
No.
Parameter
Setup range
Unit
Function
5
10
Sequence at alarm
0
7
To set up the states during the deceleration and after the stop when
an alarm occurs.
The immediate stop is valid when the parameter is set to either 4, 5,
6 or 7.
(2) Item
• Details of Pr5.10 “Sequence at alarm”
Pr5.10
During deceleration
*3
After stop
Position deviation/
external scale
deviation
0
~
3
Dynamic brake (DB)
applied
Dynamic brake (DB)
applied
Cleared *1
4
~
7
Operation A:
Instantaneous stopping
Operation B:
DB operation *2
Dynamic brake (DB)
applied
Cleared *1
*1 Position deviations/external scale deviations at the time when an alarm occurs will be retained while the alarm is still
there, and they will be cleared when the alarm is cleared.
*2 The selection of the operation A or B shows whether an immediate stop is executed. An alarm that necessitates an
immediate stop will prompt the operation A, an immediate stop, if the setting value is 4, 5, 6 or 7. An alarm that
does not require an immediate stop will result in the actions specified with the operation B; i.e. either application of
the dynamic brake (DB) or free-run. (Refer to section 6-5-5.)
Hold the main circuit power until deceleration stop is completed.
Refer to 7-1 “List of Protective Functions” for alarms that require an immediate st
*3 “During deceleration” refers to the section from the state where the motor is operating until the speed is reduced to 30
r/min or below. Once the speed reduction achieves 30 r/min and thus it transfers to the “After stop” state, the
post-stop actions will be performed regardless of the motor speed.