SR-ZSV00039
-
9
-
Motor Business Unit, Appliances Company, Panasonic Corporation
(2) Change the default assignment for output signals
To reassign an output signal, change the following parameter.
Category
No.
Parameter
Setup range
Unit
Function
4
10
SO1 output selection
0~
00FFFFFFh
-
To assign a function to the output SO1.
Set this parameter with the hexadecimal system.*1
Following the hexadecimal form, set each control mode as follows:
000000**h
Enter a function number in the place marked with "**."
Please refer to the function number table shown later in this section.
4
11
SO2 output selection
0~
00FFFFFFh
-
To assign a function to the output SO2.
Set this parameter with the hexadecimal system.
Settings can be made in the same way for Pr4.10.
4
12
SO3 output selection
0~
00FFFFFFh
-
To assign a function to the output SO3.
Set this parameter with the hexadecimal system.
Settings can be made in the same way for Pr4.10.
Function number table
Signal
Code
Setting
Invalid
-
00h
Servo
alarm output
ALM
01h
Servo ready output
S-RDY
02h
Motor holding brake release
BRK-OFF
03h
In-position
INP
04h
(
No
setting
)
-
05h
Torque limited
TLC
06h
Zero speed
ZSP
07h
(
No
setting
)
-
08h
Warning 1
WARN1
09h
Warning 2
WARN2
0Ah
Output for presence/absence of
position command
P-CMD
0Bh
In-position 2
INP2
0Ch
(
No
setting
)
-
0Dh
Alarm attribute output
ALM-ATB
0Eh
(
No
setting
)
-
0Fh
Main
power on output
P-ON
10h
Precautions:
The same function can be assigned to multiple output signals.
A control output pin set as invalid normally keeps the output transistor turned off.
Do not set any value other than set values specified in the table.
If it is set to other than set values specified in the table, Err33.4「
I
/F output function code error
will occur. And the (No setting)
in the table is set to protection function..If it is set to any values ,output will get unstable.