Characters,
Factory Default
Setting Item, Function, Setting Range
EV1 alarm value
• Sets EV1 alarm value.
Corresponds to [EV1 alarm value] in Initial setting mode.
EV1 alarm value matches EV1 low limit alarm value in the following cases:
(Alarm output, High/Low limits independent alarm),
(Alarm
output, High/Low limit range independent alarm), or
(Alarm output,
High/Low limits with standby independent alarm) is selected in [Event output EV1
allocation].
• Setting range:
High limit alarm
-(Input span) to Input span
( )
(*1) (*2)
Low limit alarm
-(Input span) to Input span
( )
(*1) (*2)
High/Low limits alarm
0 to Input span
( )
(*1) (*2)
High/Low limits independent
alarm
0 to Input span
( )
(*1) (*2)
High/Low limit range alarm
0 to Input span
( )
(*1) (*2)
High/Low limit range
independent alarm
0 to Input span
( )
(*1) (*2)
Process high alarm
Input range low limit to Input range high limit
(*1) (*3)
Process low alarm
Input range low limit to Input range high limit
(*1) (*3)
High limit with standby alarm
-(Input span) to Input span
( )
(*1) (*2)
Low limit with standby alarm
-(Input span) to Input span
( )
(*1) (*2)
High/Low limits with standby
alarm
0 to Input span
( )
(*1) (*2)
High/Low limits with standby
independent alarm
0 to Input span
( )
(*1) (*2)
[B]
Available when any alarm from
(Alarm output, High limit alarm) to
(Alarm output, High/Low
limits with standby independent alarm) is selected in [Event output EV1 allocation].
[C]
EV1 high limit alarm value
• Sets EV1 high limit alarm value.
This value is available only for the following cases:
(Alarm output, High/Low limits independent alarm),
(Alarm
output, High/Low limit range independent alarm), or
(Alarm output,
High/Low limits with standby independent alarm) is selected in [Event output EV1
allocation].
Corresponds to [EV1 high limit alarm value] in Initial setting mode.
• Setting range: Same as those of EV1 alarm value
[D]
EV1 alarm hysteresis
• Sets EV1 alarm hysteresis.
Corresponds to [EV1 alarm hysteresis] in Initial setting mode.
• Setting range: 0.1 to 1000.0
( ),
DC voltage, current inputs: 1 to 10000
(*1)
Available when any alarm from
(Alarm output, High limit alarm) to
(Alarm output, High/Low
limits with standby independent alarm) is selected in [Event output EV1 allocation].
(*1) The placement of the decimal point follows the selection.
(*2) For DC voltage and current inputs, the input span is the same as the scaling span.
(*3) For DC voltage and current inputs, input range low (or high) limit value is the same as scaling low (or high) limit value.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]