5.3 Basic Operation after Power-ON
After the unit is mounted to the control panel and wiring is completed, operate the unit following the
procedures below.
(1) Turn the unit power supply ON
※
After confirming the rated voltage, polarity and wiring, turn the power ON via contacts
such as switch or relay. If any mistakes are made, an electric shock, malfunction or errors
may be caused.
After the power is turned ON, the PV Display indicates the input type, and the SV Display indicates
the Input range high limit value (for thermocouple, RTD inputs) or Scaling high limit value (for DC
voltage, current inputs) for approximately 3 seconds. (Table 5.3-1)
During this time, all outputs and the indicators are in OFF status.
Control will then start, indicating the PV in the PV Display and SV in the SV Display.
While the control output OFF function is working, the PV Display indicates [
.].
Indication differs depending on the selection in [Indication when control output OFF].
(Table 5.3-1)
Sensor Input
PV Display
SV Display
PV Display
SV Display
K
J
R
S
B
E
T
N
PL-
C(W/Re5-26)
Pt100
JPt100
Pt100
JPt100
4 to 20 mA DC
0 to 20 mA DC
0 to 1 V DC
0 to 5 V DC
1 to 5 V DC
0 to 10 V DC
Scaling high limit value
When power is turned ON, and any errors are found, the following error codes are indicated in the
PV Display.
To
cancel
the error code, press the
key.
Error Code
Error Contents
Non-volatile IC memory is defective.
Data writing (in non-volatile IC memory) error when power failure occurs.
(2) Enter each value.
Refer to Sections ‘6. Initial Settings’ (p.29), ‘7. Settings (p.42)’ and ‘8. Operation and Settings of
Standard Functions’ (p.66).
Enter each value: Input type, Control method, Direct/Reverse action, SV, PID constants,
Event output EV1 allocation, etc.