If ‘Converter’ is selected in [Controller/Converter], this instrument can
be used as a converter, by setting the following items.
Setting Item
Values or Selection
SV1
Scaling low limit value
AT/Auto-reset Perform/Cancel
AT/AT on startup/Auto-reset Cancel
OUT1 proportional band
Scaling span
Direct current, voltage inputs: 100.0%
Integral time
0
Derivative time
0
Reset
0 (Reset value, calculated by
Auto-reset function)
OUT1 high limit
100
OUT1 low limit
0
OUT1 rate-of-change
0
OUT2 proportional band
Scaling span
Direct current, voltage inputs: 100.0%
Direct/Reverse action
Direct control action
EV1/EV2 alarm value 0
Enabled/Disabled
Disabled
EV1/EV2 alarm value
0 or Input range low limit value (Scaling
low limit value)
EV1/EV2 high limit alarm value
0 or Input range low limit value (Scaling
low limit value)
EV1/EV2 alarm hysteresis
1.0
EV1/EV2 alarm delay time
0
EV1/EV2 alarm Energized/
De-energized
Energized
Loop break alarm time
0
Loop break alarm span
0
Event output EV1 allocation
No event
Event output EV2 allocation
No event
SV rise rate
0
SV fall rate
0
OUT/OFF key function
Control output OFF function
Simplified converter
function
4 to 20 mA DC
Load resistance: Max 550