Characters,
Factory Default
Setting Item, Function, Setting Range
[57]
EV1 high limit alarm value
• Sets EV1 high limit alarm value.
This value is available only for the following cases:
(Alarm output, High/Low limits independent alarm),
(Alarm
output, High/Low limit range independent alarm), or
(Alarm output,
High/Low limits with standby independent alarm) is selected in [Event output EV1
allocation].
Corresponds to [EV1 high limit alarm value] in Initial setting mode.
• Setting range: Same as those of EV1 alarm value
[58]
EV2 alarm value
• Sets EV2 alarm value.
Corresponds to [EV2 alarm value] in Initial setting mode.
EV2 alarm value matches EV2 low limit alarm value in the following cases:
(Alarm output, High/Low limits independent alarm),
(Alarm
output, High/Low limit range independent alarm), or
(Alarm output
High/Low limits with standby independent alarm) is selected in [Event output EV2
allocation].
• Setting range: Same as those of EV1 alarm value
Available only when
(Alarm output, High limit alarm) to
(Alarm output, High/Low limits with
standby independent alarm) is selected in [Event output EV2 allocation].
[59]
EV2 high limit alarm value
• Sets EV2 high limit alarm value.
This value is available only for the following cases:
(Alarm output, High/Low limits independent alarm),
(Alarm
output, High/Low limit range independent alarm), or
(Alarm output,
High/Low limits with standby independent alarm) is selected in [Event output EV2
allocation].
Corresponds to [EV2 high limit alarm value] in Initial setting mode.
• Setting range: Same as those of EV1 alarm value
[60]
Loop break alarm time
• Sets the time to assess the Loop break alarm.
Corresponds to [Loop break alarm time] in Initial setting mode.
Refer to ‘Loop Break Alarm’ on p.40.
• Setting range: 0 to 200 minutes
Setting to 0 (zero) disables the alarm.
[61]
Loop break alarm span
• Sets the temperature to assess the Loop break alarm.
Corresponds to [Loop Break alarm span] in Initial setting mode.
Refer to ‘Loop Break Alarm’ on p.40.
• Setting range: 0 to 150
( ), 0.0 to 150.0
( )
DC voltage, current inputs: 0 to 1500
(*1)
Setting to 0 (zero) disables the alarm.
(*1) The placement of the decimal point follows the selection.