7.2 Sub Setting Mode
To enter Sub setting mode, press the
and
keys (in that order) together in RUN mode.
Use the
or
key for settings (or selections).
To register the set data, use the
key.
Explanation of setting items:
• Upper left: PV Display: Indicates setting characters.
• Lower left: SV Display: Indicates factory default value.
• Right side: Indicates the setting item, explanation of its function and setting range (or selection item).
[37]
AT/Auto-reset Perform/Cancel
• Selects AT or ‘AT on startup’ Perform/Cancel in PID control action, or Auto-reset
Perform/Cancel in P or PD control action.
Setting item numbers such as [37], [38] are the same as those on Section “14. Key Operation Flowchart”
(p.131).
Characters,
Factory Default
Setting Item, Function, Setting Range
AT/Auto-reset Perform/Cancel
• Selects AT or ‘AT on startup’ Perform/Cancel in PID control action, or Auto-reset
Perform/Cancel in P or PD control action.
Refer to Sections ‘8.5 Setting PID Constants (by Performing AT)’ (p.70), and
‘8.6 Performing Auto-reset’ (p. 73).
• Selection item:
AT/AT on startup/Auto-reset Cancel
AT Perform
‘AT on startup’ Perform
Auto-reset Perform
[37]
Not available for ON/OFF control or PI control.
[38]
OUT1 proportional band
• Sets OUT1 proportional band.
• Setting range: 0 to Input span
( )
DC voltage, current inputs: 0.0 to 1000.0%
OUT1 becomes ON/OFF control when set to 0 or 0.0.
[39]
Integral time
• Sets the integral time.
Auto-reset can be performed when PD is control action (I = 0).
• Setting range: 0 to 3600 seconds
Setting the value to 0 disables integral action.
Not available if OUT1 is in ON/OFF control.
[40]
Derivative time
• Sets the derivative time.
• Setting range: 0 to 1800 seconds
Setting the value to 0 disables derivative action.
Not available if OUT1 is in ON/OFF control.
Setting characters
Factory default value
Setting item name, function, setting range (or selection item)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]