7. Settings
In this section, Main setting, Sub setting and Engineering mode 1 and 2 will be explained.
7.1 Main Setting Mode
To enter Main setting mode, press the
key in RUN mode.
Use the
or
key for settings (or selections).
To register the set data, use the
key.
Explanation of setting items:
• Upper left: PV Display: Indicates setting characters.
• Lower left: SV Display: Indicates factory default value.
• Right side: Indicates the setting item, explanation of its function and setting range (or selection item).
[10]
SV1
• Sets SV1.
• Setting range: Scaling low limit to Scaling high limit
Setting item numbers such as [10], [11] are the same as those on Section “14. Key Operation Flowchart”
(p.131).
Characters,
Factory Default
Setting Item, Function, Setting Range
[10]
SV1
• Sets SV1.
• Corresponds to [SV1] in Initial setting mode.
If Program control is selected in [OUT/OFF key function], this will become Step 1
SV.
• Setting range: Scaling low limit to Scaling high limit
(*1)
[11]
Step 1 time
• Sets Step 1 time.
• Setting range:
, or 00:00 to 99:59
If
is set, Step 1 time will be held, and Fixed value control will be performed
using Step 1 SV.
Available only when Program control is selected in [OUT/OFF key function].
[12]
Step 1 wait value
• Sets Step 1 wait value.
• Setting range: 0 to Converted value of 20% of the input span
DC voltage, current inputs: 0 to Converted value of 20% of scaling span
(*1)
Setting the value to 0 disables this Wait function.
Available only when Program control is selected in [OUT/OFF key function].
(*1) The placement of the decimal point follows the selection.
Setting characters
Factory default value
Setting item name, function, setting range (or selection item)