5.6.2 Statuses and Measures
The statuses judged by the self-monitoring function are classified into the following four
categories.
When the status is “notification”, “caution”, or “fault”, you must check the installation state or
maintain or replace the product.
Status
Description
Remarks
Normal
Normal state
The device is operating normally.
Notification
Unstable detection state
Review the settings.
Caution
State in which the device must be replaced
The device has almost reached its service life.
Fault
State in which the device is uncontrollable
The device is short-circuited or broken.
If “notification”, “caution”, or “fault” status is notified, take measures as shown in the following
table.
Response parameter
Measures
Refere
nce
page
Measurement
alarm
Notif
icati
on
Sensor head unconnected
Status check
E200
–
Connected sensor head incompatible Status check
E230
–
Connected unit count check error
Status check
E160 (For
master units
only)
–
NPN / PNP output type mixture error
Status check
E100 (For
master units
only)
–
Calculated unit count error
Status check
E110 (For
master units
only)
–
Copy execution error (Slave unit
problem)
Status check
E170 (For
master units
only)
–
Detection capability limit (obtained
edge information)
Sensing object
check
–
Measurement
alarm 1
The amount of entering light is too
much due to the influences of
ambient light, etc.
Status check
–
Measurement
alarm 1
The amount of entering light
decreases due to stain on the
detection surface, beam axis
misalignment, etc.
Sensing object
check
–
Measurement
alarm 2
The specified measurement direction
differs from the insertion direction of
the detected object.
Status check /
Sensing object
check
–
Measurement
alarm 2
CAU
TIO
N
Controller cumulative run time limit
exceeded
(87,600 hours)
Controller
replacement
–
–
5.6 Self-monitoring Function
5-48
WUME-HGT-6
Содержание HG-T Series
Страница 2: ... MEMO 2 WUME HGT 6 ...
Страница 28: ... MEMO 2 8 WUME HGT 6 ...
Страница 96: ... MEMO 5 50 WUME HGT 6 ...
Страница 99: ... Note 2 Displayed only during calculation 6 1 Flow of Measurement Data WUME HGT 6 6 3 ...
Страница 128: ... MEMO 6 32 WUME HGT 6 ...
Страница 158: ... No timer OFF 7 2 Advanced Settings 7 30 WUME HGT 6 ...
Страница 177: ...Example Positioning a glass plate Setting method 7 2 Advanced Settings WUME HGT 6 7 49 ...
Страница 218: ...8 2 3 Side View Attachment HG TSV10 Units mm 8 2 Dimension Drawings 8 14 WUME HGT 6 ...
Страница 221: ...10 Troubleshooting 10 1 Troubleshooting 10 2 10 2 Error Messages 10 5 WUME HGT 6 10 1 ...
Страница 228: ...Menu Structure General Function Display Menu Structure General Function Display App 2 WUME HGT 6 ...
Страница 229: ...Menu Structure General Function Display WUME HGT 6 App 3 ...
Страница 230: ...Menu Structure Extended Function Display Menu Structure Extended Function Display App 4 WUME HGT 6 ...
Страница 231: ...Menu Structure Extended Function Display WUME HGT 6 App 5 ...
Страница 232: ... MEMO App 6 WUME HGT 6 ...
Страница 235: ... MEMO WUME HGT 6 ...
Страница 236: ...Panasonic Industrial Devices SUNX Co Ltd 2020 PRINTED IN JAPAN WUME HGT 6 ...