Wiring of Power Supply and General-purpose I/O Parts
5-10
Precautions when using a reed switch with LED
If the LED is connected in series to the input contacts (such as a reed switch with LED, etc.),
apply a voltage greater than the ON voltage to the input terminal of the PLC. Please pay
special attention when several switches are connected in series.
Reed switch with LED
Input terminal
COM terminal
+
ON voltage
or more
PLC
Input power
LED
contact
Precautions when using a two-wire sensor
When using a two-wire photoelectric sensor or proximity sensor, if cutting off the input current
flowing to PLC is not possible due to the leakage current, connect the bleeder resistor as
shown in the left chart.
Input terminal
COM terminal
+
Bleeder resistor
R
PLC
Two-wire
sensor
Inte
rna
l
circ
uit
Precautions when using a limit switch with LED
When using a limit switch with LED, if cutting off the input current flowing to PLC is not
possible due to the leakage current, connect the bleeder resistor as shown in the left chart.
Input terminal
COM terminal
Input power
+
Bleeder resistor
R
r
PLC
Limit
switch
with LED
Inte
rna
l
circ
uit
Содержание FP-XH M8N16PD
Страница 1: ......
Страница 23: ...1 System Structure ...
Страница 39: ...2 Control Unit Specifications ...
Страница 48: ...Control Unit Specifications 2 10 ...
Страница 49: ...3 I O Allocation ...
Страница 77: ...4 Installation ...
Страница 89: ...5 Wiring of Power Supply and General purpose I O Parts ...
Страница 104: ...Wiring of Power Supply and General purpose I O Parts 5 16 ...
Страница 105: ...6 Wiring of Motion I O Parts ...
Страница 116: ...Wiring of Motion I O Parts 6 12 ...
Страница 117: ...7 Power On Off and Check Items ...
Страница 124: ...Power On Off and Check Items 7 8 ...
Страница 125: ...8 Steps Before Running ...
Страница 134: ...Steps Before Running 8 10 KEYPOINTS Port No can be confirmed through the computer s device manager ...
Страница 142: ...Steps Before Running 8 18 ...
Страница 143: ...9 Setting of Position Control Parameters ...
Страница 159: ...10 Transfer to Unit and Commissioning ...
Страница 181: ...11 Automatic Operation Position Control ...
Страница 193: ...11 2 Interpolation Control 11 13 ...
Страница 209: ...12 Automatic Operation Synchronous Control ...
Страница 251: ...13 Manual Operation JOG Operation ...
Страница 256: ...Manual Operation JOG Operation 13 6 ...
Страница 257: ...14 Manual Operation Home Return ...
Страница 264: ...Manual Operation Home Return 14 8 ...
Страница 265: ...15 Pulse Input Function ...
Страница 278: ...Pulse Input Function 15 14 ...
Страница 279: ...16 Stop Function ...
Страница 285: ...17 Auxiliary Function ...
Страница 326: ...Auxiliary Function 17 42 Note Refer to the latest instruction manual and technical materials of the servo amplifier ...
Страница 329: ...18 Instruction Reference ...
Страница 357: ...19 Error Warning Annunciation Function ...
Страница 386: ...Error Warning Annunciation Function 19 30 ...
Страница 387: ...20 Troubleshooting ...
Страница 402: ...Troubleshooting 20 16 ...
Страница 403: ...21 Memory Master Memory Cassette ...
Страница 418: ...Memory Master Memory Cassette 21 16 ...
Страница 419: ...22 Security Functions ...
Страница 430: ...Security Functions 22 12 ...
Страница 431: ...23 General purpose Input High speed counter Function ...
Страница 448: ...General purpose Input High speed counter Function 23 18 ...
Страница 449: ...24 Other Functions ...
Страница 452: ...Other Functions 24 4 ...
Страница 453: ...25 Maintenance and Inspection ...
Страница 457: ...26 Specifications ...
Страница 552: ...Specifications 26 96 ...
Страница 553: ...Record of changes Manual No Date Record of Changes WUME FPXHM8N16PD 01 Sep 2017 First Edition ...
Страница 554: ......
Страница 555: ......
Страница 556: ......