Note
●
To connect the cable (B), be sure to put the polarity marking
side of the duct on the grounding side.
●
if the polarity is changed by processing the duct end or
using he auxiliary duct unit (DH2310), the arrangement of
terminals of the feed-in cap will be inverted.
●
he cable (A) must be 14 to 38 mm
2
in size.
●
The cable (B) must be a single-conductor cable of 1.6 to
2.0 mm in size or a stranded-conductor cable of 2 to 3.5
mm
2
in size.
●
To use a terminal plug with a remote control circuit breaker,
apply a 100V operating voltage. (200V operating voltage is
not available for this product.)
●
Connect a grounding cable to the grounding terminal screw
by the use of a crimp-style terminal or winding the cable
around the terminal.
Installing feed-in cap
Put a feed-in cap in the Factory Line duct, and then
fasten the setscrews to fix the cap.
6
●
Securely fasten the setscrews and terminal screws.
Doing so may result in an electric shock, or a fire
Caution
Cover
Electrical cable(B)
Electrical cable(A)
Terminal
Terminal screw (A)
Terminal
screw (B)
Feed-in cap
Washer
Setscrew
Grounding
terminal screw
Polarity indication
(Grounding side)
(Green line)
Connecting to Factory Line duct
1
.Strip the sheath of the electrical cable (A) by 18 to 20 mm
in length, unfasten the terminal screw (A) to put the
electrical cable (A) in the terminal, and then fasten the
terminal screw (A) to securely connect the electrical cable (A).
After connecting,post the polarity indication label near the
screw terminals.(Tightening torque 5.0 N ・ m 〜 7.0 N ・ m)
2
.Strip the sheath of the electrical cable (B) by 10 to 12 mm
in length, unfasten the terminal screw (B) to put the
electrical cable (B) under the washer, and then fasten the
terminal screw (B) to securely connect the electrical cable (B).
(Tightening torque 2.1 N ・ m 〜 2.6 N ・ m)
3
.Mount the cover to the feed-in cap.
Connecting cables
Feed-in Cap
Put the polarity indication label
Duct
The plug front
The plug
right side
The plug
left side
Polarity indication
(Green line)
Polarity indication label
24