1
.Remove the setscrews, and then dismount the cover.
2
.Unfasten the cable clamp securing screw, and then put the cables in the cover.
3
.Connect the cables to the terminal block by the use of a crimp-style
terminal or winding the cable around the terminal, respectively.
After connecting,post the polarity indication label near the terminals
screw.(Tightening torque 4.0 N ・ m 〜 5.0 N ・ m)
4
.Mount the cover to the main body on the terminal
plug A side, and then fix it with the setscrews.
5
.Fasten the securing screw of the cable clamp to fix the cables.
Lever
(Green)
Body
Terminal
screw
(M6)
Terminal
block
Grounding
terminal screw
Grounding terminal block
is located on the back.
Cover
Setscrew
Securing screw
Cable clamp
Polarity indication
(Grounding side)(Green line)
Polarity indication
(Grounding side)
(Green line)
Ground
Body
Notes
●
Use cables of 3.5 mm
2
to 5.5 mm
2
in size.
●
Connect a single core to the grounding terminal block.
Mounting terminal plug A
9
Connecting cables
●Put the plug lever (green) in the duct in line with its polarity marking
(green line), and then rotate it clockwise by 90 degrees.
Mounting plug
●Pull down the plug lever, and then rotate it
counterclockwise by 90 degrees.
Dismounting plug
Mounting 30A plug
Mounting 60A plug
●Put the lever (green) on each side of the duct in the duct in line with its polarity marking
(green line), and then rotate it outwards by 90 degrees (until you feel a click).
1 Adjust the polarity
2 Insert
3 Rotate90° clockwise
1 Adjust the
polarity
2 Insert
Caution
●
Securely fasten the terminal screws.
●
Do not use plugs (with an orange lever) for Factory Line 30.
●
Do not mount the plug in the opposite direction.
Doing so may result in an electric shock or a fire.
Caution
●
Securely fasten the terminal screws.
●
Do not use plugs (with an orange lever) for Factory Line 30.
●
Do not mount the plug in the opposite direction.
Doing so may result in an electric shock or a fire.
●Pull down the lever on each side of the duct, and then rotate it
inwards by 90 degrees (until you feel a click) to pull out the plug.
Dismounting plug
1
.Remove the setscrews, and then dismount the cover.
2
.Unfasten the cable clamp securing screw, and then put the cables in the cover.
3
.Connect the cables to the terminal block by the use of a crimp-style
terminal or winding the cable around the terminal, respectively.
After connecting,post the polarity indication label near the terminals
screw.(Tightening torque 4.0 N ・ m 〜 5.0 N ・ m)
4
.Mount the cover to the main body on the terminal
plug A side, and then fix it with the setscrews.
5
.Fasten the securing screw of the cable clamp to fix the cables.
Notes
●
Use cables of 5.5 mm
2
to 14 mm
2
in size in accordance with load capacity.
●
Connect a single core to the grounding terminal block by the use of a crimp-style terminal.
Connecting cables
Mounting plug
Terminal
block
Setscrew
Terminal
Grounding
terminal block
Cover
Securing screw
Cable clamp
Lever
(Green)
Grounding
terminal screw
3
Rotate by
90 degrees.
Polarity indication
(Grounding side)
(Green line)
Ground
(Green)
Lever
Feed-in Cap
Put the polarity indication label
Duct
The plug front
Polarity indication
(Green line)
Put the polarity indication label
Terminal screw
(M5)
The plug
left side
The plug
right side
22