Securely fasten the terminal screws.
●
Do not use plugs (with an orange lever) for Factory Line 30.
●
Do not mount the plug in the opposite direction.
Doing so may result in an electric shock or a fire.
Caution
Polarity indication
(Grounding side)
(Green line)
Lever
(Green)
Terminal
screw
(M5)
Terminal
block
Cable clamp
Ground
Ground
Body
Grounding
terminal screw
Grounding
terminal block
Cover
Setscrew
Securing screw
Mounting a circuit breaker equipped terminal plug
10
Thoroughly check for the direction
to mount the plug.
■2P Type
2P20A200V with ground
2P30A200V with ground
Polarity indication
(Green line)
Lever
(Green)
Body
Grounding
terminal screw
Grounding
terminal block
Terminal block
Terminal screw
(M6)
Cover
Setscrew
Securing screw
Cable clamp
Mounting 20・30A plug
Mounting 60A plug
Connecting cables
Mounting plug
●Pull down the plug
lever, and then rotate
it counterclockwise
by 90 degrees.
Dismounting plug
Connecting cables
●Put the lever (green) on each side of the
duct in line with its polarity marking (green
line), and then rotate it outwards by 90
degrees (until you feel a click).
Mounting plug
●Pull down the lever on each side
of the duct, and then rotate it
wardsby 90 degrees (until you
feel a click) to pull out the plug.
Dismounting plug
1 Adjust the polarity.
2 Insert
3 Rotate by
90 degrees.
Polarity indication
(Green line)
Feed-in Cap
Put the polarity indication label
Duct
Polarity indication
(Green line)
Put the polarity indication label
2 Insert
3 Rotate90° clockwise
1 Adjust the polarity
ⅠTYPE
ⅡTYPE
ⅢTYPE
Polarity indication
(Grounding side)
(Green line)
1
.Remove the setscrews, and then dismount the cover.
2
.Unfasten the cable clamp securing screw, and then
put the cables in the cover.
3
.Connect the cable to the terminal block.
When using a stranded-conductor cable or a crimp-style terminal (applicable
crimp-style terminal : 5.5 - 5 ), connect them to both of the terminal screws.
Fasten the terminal screws (tightening torque: 2.5 N•m ‒ 3.5 N•m). After
connecting them, post the polarity indication labels near the terminal screws.
4
.Mount the cover to the main body on circuit breaker
equipped terminal plug, and then fix it with the setscrews.
5
.Fasten the securing screw of the cable clamp to
fix the cables.
Notes
●
Securely fasten the terminal screws.
●
Do not use plugs (with an orange lever) for Factory Line 30.
●
Do not mount the plug in the opposite direction.
Doing so may result in an electric shock or a fire.
Caution
●
Use cables of 5.5 mm
2
in size in accordance with load capacity.
●
Connect a single core to the grounding terminal block.
●
Do not subject the plug to intense shocks or vibrations.
●Put the plug lever (green) in the
Factory line duct in line with its
polarity marking (green line), and then
rotate it clockwise by 90 degrees.
single-conductor
cable
stranded-conductor
cable
crimp-style
terminal
1
.Remove the setscrews, and then dismount the cover.
2
.Unfasten the cable clamp securing screw, and then put the cables in the cover.
3
.
Connect the cable to the terminal block.
When using a stranded-conductor cable or a crimp-style terminal (applicable
crimp-style terminal : 14 - 6 ), connect them to both of the terminal screws.
Fasten the terminal screws (tightening torque: 4.0 N•m ‒ 5.0 N•m). After
connecting them, post the polarity indication labels near the terminal screws.
4
.Mount the cover to the main body on circuit breaker equipped
terminal plug, and then fix it with the setscrews.
5
.Fasten the securing screw of the cable clamp to fix the cables.
single-conductor
cable
stranded-conductor
cable
crimp-style
terminal
Notes
●
Use cables of 14 mm
2
in size in accordance
with load capacity.
●
Connect a single core to the grounding terminal block.
●
Do not subject the plug to intense shocks or vibrations.
Lever
(Green)
The plug front
The plug
left side
The plug
right side
20
21