36
Installation Manual
Step 1. If not completed already from earlier, connect the other end of the
battery connection cable to the large terminal block located in the battery
enclosure. See image below.
Step 2. Connect the four red wires to the battery positive binding post.
Connect the four black wires to the battery negative binding post. The
smaller/shorter wires go to the top batteries. The longer/larger wires go
to the bottom batteries.
CAUTION:
Before making the final connection or closing the
breaker, make sure the connections have the correct polarity.
Check polarity labels above.
CAUTION:
Do
NOT
apply anti-oxidant substance on the
terminals before terminals are connected tightly.
CAUTION:
Do not place anything between the flat part of
the inverter terminal and the ring terminal. Otherwise,
overheating may occur.
WARNING:
Check positive (+) and the negative (-) terminals.
If the EverVolt is connected with reversed polarity, unexpected
reactions may occur such as damages, heat generation,
smoke, fire, or explosion.
WARNING:
Do not connect between the positive (+) and
negative (-) terminals with a conductive material (e.g. wire,
a cable, etc.). This may result in damages, heat generation,
smoke, fire, or explosion.
Battery Connection & Charging Requirements
Содержание EverVolt Standard EVAC-105-4
Страница 49: ...49 Installation Manual 11 SAMPLE WIRING DIAGRAM Wiring Diagram EVERVOLT MINI STANDARD PLUS ...
Страница 54: ...54 Installation Manual Operation and Display Panel ...
Страница 66: ...66 Installation Manual Configuring the Hardware ...
Страница 68: ...68 Installation Manual Internet Connectivity Options Included PLC option ...
Страница 75: ...75 Installation Manual ...