29
Installation Manual
Connections
4. CONNECTIONS
• Make sure the circuit breaker is off before making or modifying any
connections.
• To prevent the risk of electric shock, make sure the ground wire
is properly earthed before operating this unit whether the grid is
connected or not.
• To reduce the risk of injury, use the recommended wire/cable size.
• Do not apply anti-oxidant substance on battery terminals connections
are made.
WARNINGS
GRID
LOAD
BATTERY
SIZE
8 AWG
8 AWG
2 AWG
LENGTH
--
--
Use 6ft
cable. If
longer cable
is needed,
make sure it
is less than
16 ft.
Wire/Cable Requirements
Strip 15mm(0.6in) off the AC wires and battery cables.
Notes
• Order of connections should be Grid, Load, then Battery.
• Order of wire connections should be Ground, N, L1, L2.
• Connect AC wires according to the labels on the terminal block or
your system