17.4.25 F99 (Output Over Current Detection)
Malfunction Decision Conditions
During operation of cooling and heating, when an output over-current (DC peak current value at IPM Prevention
Control) is detected by checking the current that flows in the inverter DC peak sensing circuitry.
Malfunction Caused
Faulty outdoor unit PCB
Faulty
compressor
Troubleshooting
Checking the power transistor
Never touch any live parts for at least 10 minutes after turning off the circuit breaker.
If unavoidable necessary to touch a live part, make sure the power transistor’s supply voltage is below 50V using
the tester.
For the UVW, make measurement at the Faston terminal on the board of the relay connector.
Tester’s negative terminal
Power transistor (+)
UVW
Power transistor (-)
UVW
Tester’s positive terminal
UVW
Power transistor (+)
UVW
Power transistor (-)
Normal resistance
Several k
Ω
to several M
Ω
Abnormal resistance
0 or
∞
Содержание CS-MRE7PKE
Страница 15: ...15 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit...
Страница 17: ...17 5 2 Outdoor Unit...
Страница 18: ...18 6 Refrigeration Cycle Diagram...
Страница 19: ...19 7 Block Diagram 7 1 Indoor Unit...
Страница 20: ...20 7 2 Outdoor Unit...
Страница 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 22: ...22 8 2 Outdoor Unit...
Страница 23: ...23 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 24: ...24 9 2 Outdoor Unit...
Страница 26: ...26 10 2 Outdoor Unit...
Страница 53: ...53 17 3 Self Diagnosis Function...
Страница 54: ...54...
Страница 87: ...87...
Страница 88: ...88 19 1 1 2 CS MRE9PKE...
Страница 89: ...89...
Страница 90: ...90 19 1 2 Two Indoor Unit Operation 19 1 2 1 CS MRE7PKE x2...
Страница 91: ...91...
Страница 92: ...92 19 1 2 2 CS MRE9PKE CS MRE7PKE...
Страница 93: ...93...
Страница 94: ...94 19 2 Operation Characteristics CU 2RE18PBE 19 2 1 One Indoor Unit Operation 19 2 1 1 CS MRE7PKE...
Страница 95: ...95...
Страница 96: ...96 19 2 1 2 CS MRE9PKE...
Страница 97: ...97...
Страница 98: ...98 19 2 1 3 CS MRE12PKE...
Страница 99: ...99...
Страница 100: ...100 19 2 2 Two Indoor Unit Operation 19 2 2 1 CS MRE7PKE x2...
Страница 101: ...101...
Страница 102: ...102 19 2 2 2 CS MRE9PKE x2...
Страница 103: ...103...
Страница 104: ...104 19 2 2 3 CS MRE12PKE x2...
Страница 105: ...105...