background image

109 

SAFETY  REF. NO. 

PART NAME & DESCRIPTION 

QTY. 

CU-2RE15PBE 

CU-2RE18PBE 

REMARK

 

CHASSIS ASSY 

CWD52K1277 

 

 

FAN MOTOR BRACKET 

CWD541167 

 

 

FAN MOTOR, AC 50W SINGLE 

ARW6405AC 

 

 

3a 

SCREW-FAN MOTOR BRACKET 

CWH551217 

 

 

3b 

SCREW-FAN MOTOR MOUNT 

CWH55252J 

 

 

PROPELLER FAN 

CWH03K1066 

 

 

NUT - PROPELLER FAN 

CWH56053J 

 

 

COMPRESSOR 

5RD132XFC21 

 

 

ANTI - VIBRATION BUSHING 

CWH50077 

 

 

NUT - COMPRESSOR 

CWH56000J 

 

 

SOUND PROOF MATERIAL 

CWG302808 

 

 

10 

SOUND PROOF MATERIAL 

CWG302630 

 

 

11 

SOUND PROOF MATERIAL 

CWG302806 

 

 

12 

SOUND PROOF MATERIAL 

CWG302807 

 

 

13 

CONDENSER COMPLETE 

CWB32C3722 

 

 

14 

CRANKCASE HEATER 

CWA341044 

 

 

15 

RECEIVER 

CWB14011 

 

 

18 

STRAINER 

CWB111024 

 

 

19 

EXPANSION VALVE 

CWB051029 

 

 

20 

4-WAYS VALVE 

CWB001064 

 

 

21 

STRAINER 

CWB111004 

 

 

22 

STRAINER 

CWB111080 

 

 

24 

V-COIL COMPLETE (EXPAND VALVE-WHITE) 

CWA43C2579 

 

 

25 

V-COIL COMPLETE (EXPAND VALVE-YELLOW) 

CWA43C2580 

 

 

26 

V-COIL COMPLETE (4 WAY VALVE) 

CWA43C2585 

 

 

27 

SOUND-PROOF BOARD 

CWH151366 

 

 

29 

SENSOR-COMPLETE - INTAKE & PIPE 

CWA50C2893 

 

 

31 

SENSOR-COMPLETE - GAS 

CWA50C3070 

 

 

32 

SENSOR-COMPLETE - DEF. 

CWA50C3069 

 

 

33 

HOLDER-SENSOR 

CWH32143 

 

 

34 

SENSOR-COMPLETE - TANK 

CWA50C2894 

 

 

35 

NORMAL-MODE LINE CHOKE COILS 

G0C193J00004 

 

 

36 

ELECTRONIC CONTROLLER 

CWA73C7217R 

CWA73C7218R 

 

37 

TERMINAL BOARD ASS'Y 

CWA28K1162 

 

 

38 

TERMINAL BOARD ASS'Y 

CWA28K1161 

 

 

40 

CONTROL BOARD COVER 

CWH131473 

 

 

41 

TERMINAL COVER 

CWH171039A 

 

 

43 

3-WAY VALVE (LIQUID) 

CWB011418 

 

 

44 

3-WAY VALVE (GAS) 

CWB011081J 

 

 

45 

HOLDER COUPLING 

CWH351253 

 

 

46 

NUT - TERMINAL COVER 

CWH7080300J 

 

 

47 

CABINET TOP PLATE 

CWE031148A 

 

 

48 

CABINET FRONT PLATE CO. 

CWE06C1468 

 

 

49 

CABINET SIDE PLATE COMP 

CWE04C1453 

 

 

50 

CABINET SIDE PLATE 

CWE041579A 

 

 

51 

CONTROL BOARD COVER COMPLETE 

CWH13C1300 

 

 

52 

SENSOR-COMPLETE - LIQUID 

 

 

53 

WIRE NET 

CWD041166A 

 

 

54 

BAG-COMPLETE 

CWG87C900 

 

 

55 

BAG 

CWG861078 

 

 

56 

BASE BOARD-COMPLETE 

CWG62C1144 

 

 

57 

SHOCK ABSORBER ( R ) 

CWG713415 

 

 

58 

SHOCK ABSORBER ( L ) 

CWG713416 

 

 

59 

C.C. CASE 

CWG566848 

 

 

60 

OPERATING INSTRUCTION 

CWF568939 

 

Содержание CS-MRE7PKE

Страница 1: ...This service information is designed for experienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to advise non technical individu...

Страница 2: ...n control Cool 44 15 2 Dew Prevention control Cool 44 15 3 Electronic Parts Temperature Rise Protection 1 Cool 44 15 4 Electronic Parts Temperature Rise Protection 2 Cool 44 15 5 Cooling overload cont...

Страница 3: ...commended to be installed with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakdown 10...

Страница 4: ...door unit air inlet and aluminium fin It may cause injury 5 Select an installation location which is easy for maintenance 6 Pb free solder has a higher melting point than standard solder typically the...

Страница 5: ...se H L dB A 40 29 40 29 Power Level dB 56 56 Indoor Fan Type Cross flow Fan Cross flow Fan Material ASG20K1 ASG20K1 Motor Type DC 8 poles DC 8 poles Input Power W 47 3 47 3 Output Power W 40 40 Speed...

Страница 6: ...y Bulb Wet Bulb Dry Bulb Wet Bulb Indoor Operation Range Cooling Maximum C 32 23 32 23 Minimum C 16 11 16 11 Heating Maximum C 30 30 Minimum C 16 16 1 Cooling capacities are based on indoor temperatur...

Страница 7: ...l ASG20K1 Motor Type DC 8 poles Input Power W 47 3 Output Power W 40 Speed QLo Cool rpm 790 Heat rpm 790 Lo Cool rpm 870 Heat rpm 870 Me Cool rpm 1070 Heat rpm 1090 Hi Cool rpm 1260 Heat rpm 1300 SHi...

Страница 8: ...ooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet B...

Страница 9: ...ent A 12 0 Maximum Input Power W 2 73k Starting Current A 6 10 Circuit Breaker Capacity A 16 Dimension Height mm 619 Width mm 824 70 Depth mm 299 Net Weight kg 39 Connection Cable 3 1 Earth 1 5 mm 2 P...

Страница 10: ...nge Cooling Maximum C 32 23 Minimum C 16 11 Heating Maximum C 30 Minimum C 16 Outdoor Operation Range Cooling Maximum C 43 26 Minimum C 16 11 Heating Maximum C 24 18 Minimum C 10 11 Note Specification...

Страница 11: ...ent A 12 0 Maximum Input Power W 2 73k Starting Current A 6 95 Circuit Breaker Capacity A 16 Dimension Height mm 619 Width mm 824 70 Depth mm 299 Net Weight kg 39 Connection Cable 3 1 Earth 1 5 mm 2 P...

Страница 12: ...nge Cooling Maximum C 32 23 Minimum C 16 11 Heating Maximum C 30 Minimum C 16 Outdoor Operation Range Cooling Maximum C 43 26 Minimum C 16 11 Heating Maximum C 24 18 Minimum C 10 11 Note Specification...

Страница 13: ...oom 1 Room Indoor Unit Capacity kW Total Indoor Capacity kW Indoor Unit Capacity kW Total Indoor Capacity kW 20 20 40 20 20 20 25 45 25 25 20 32 52 32 32 25 25 50 Indoor Unit CS MRE7 9 12PKE Outdoor U...

Страница 14: ...ong piping up to 15 meters 0 75 1 75HP during single split connection only Easy to use remote control Quality Improvement o Random auto restart after power failure for safety restart operation o Gas l...

Страница 15: ...15 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...

Страница 16: ...16 5 Dimensions 5 1 Indoor Unit...

Страница 17: ...17 5 2 Outdoor Unit...

Страница 18: ...18 6 Refrigeration Cycle Diagram...

Страница 19: ...19 7 Block Diagram 7 1 Indoor Unit...

Страница 20: ...20 7 2 Outdoor Unit...

Страница 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit...

Страница 22: ...22 8 2 Outdoor Unit...

Страница 23: ...23 9 Electronic Circuit Diagram 9 1 Indoor Unit...

Страница 24: ...24 9 2 Outdoor Unit...

Страница 25: ...25 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 2 Indicator and Receiver Printed Circuit Board...

Страница 26: ...26 10 2 Outdoor Unit...

Страница 27: ...s of the Outdoor Unit Have Been Changed Accompanying the changes in the shapes of the 3 way valve caps the tightening method has also been changed Firmly tighten the 3 way valve caps by hand and then...

Страница 28: ...or Unit Have Been Changed Accompanying the changes in the shapes of the 3 way valve caps the tightening method has also been changed Firmly tighten the 3 way valve caps by hand and then tighten them u...

Страница 29: ...vent direct sunlight or rain be careful that heat radiation from the condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces i...

Страница 30: ...ate horizontally by aligning the marking off line with the thread and using a level gauge 2 Drill the piping plate hole with 70 mm hole core drill o Line according to the left and right side of the in...

Страница 31: ...31 12 2 3 1 For the right rear piping 12 2 3 2 For the right and right bottom piping 12 2 3 3 For the embedded piping This can be used for left rear piping and bottom piping also...

Страница 32: ...3 Bind all the indoor and outdoor connection cable with tape and route the connection cable via the escapement 4 Remove the tapes and connect the connection cable between indoor unit and outdoor unit...

Страница 33: ...cutter and then remove the burrs 2 Remove the burrs by using reamer If burrs is not removed gas leakage may be caused Turn the piping end down to avoid the metal powder entering the pipe 3 Please make...

Страница 34: ...to the copper pipe In case of using long piping Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten the flare nut with torque wrench in sp...

Страница 35: ...m with a torque wrench 7 Remove the valve caps of both of the 3 way valve Position both of the valves to OPEN using a hexagonal wrench 4 mm 8 Mount valve caps onto the both 3 way valve o Be sure to c...

Страница 36: ...equipment must be properly earthed Note Isolating Devices Disconnecting means should have minimum 3 0 mm contact gap Earth wire shall be Yellow Green Y G in colour and longer than other AC wires for...

Страница 37: ...nd it is updated continuously whenever the electrical power is supplied to the unit 13 1 2 Cooling Operation 13 1 2 1 Thermostat control Capability supply to indoor unit is OFF Expansion valve closed...

Страница 38: ...temperature During operation mode judgment indoor fan motor with speed of Lo and outdoor fan motor are running for 30 seconds to detect the indoor intake and outdoor air temperature The operation mod...

Страница 39: ...rection is determined by operation mode heat exchanger temperature and intake air temperature and manual angles of direction can be adjusted using remote control 13 4 1 Vertical Airflow Operation Mode...

Страница 40: ...imer can be set using remote control the unit with timer set will stop operate at set time 13 6 Auto Restart Control When the power supply is cut off during the operation of air conditioner the compre...

Страница 41: ...onditions o When either one of the start conditions are not complied 14 1 3 Cooling Powerful Operation 1 During cooling operation this control is to concentrate outdoor unit capability to the powerful...

Страница 42: ...ooling heating operation this control is to provide fast cooling heating operation compare to normal operation Operation start if all condition below are complied o Powerful operation ON for indoor un...

Страница 43: ...or higher than Lo fan o 1 operation indoor unit o In any cooling overload zone o During annual cooling o Initial frequency operation o During starting control o During Electronic part temperature ris...

Страница 44: ...during cooling overload condition Start conditions o Outdoor ambient temperature is at protection region as shown in figure below o Outdoor unit total current is above 5 5A 4E 3E 5 0A 2E18 2E15 Contr...

Страница 45: ...n This control detect outdoor ambient temperature and perform the fan speed adjustment during heating operation 15 7 Extreme Low Temperature Compressor low pressure protection control Heat This contro...

Страница 46: ...frequency will increase However if total outdoor unit running current exceeds Y value compressor will be stopped immediately for 3 minutes Operation Mode CU 2RE18PBE CU 2RE15PBE X A Y A X A Y A Coolin...

Страница 47: ...all indoor units 15 15 Valve close detection control This control detects 3 way valve close condition to prevent damage to refrigerant cycle Start conditions o For all connected indoor units if Indoor...

Страница 48: ...3 REMOTE CONTROL NUMBER SWITCH MODE The Remote Control Number Switch Mode will be activated if the Auto OFF ON button is pressed continuously for more than 11 seconds 3 beep sounds will occur at 11th...

Страница 49: ...mote Control Receiving Sound OFF ON Mode is restarted 16 2 Remote Control Button 16 2 1 SET BUTTON To check remote control transmission code and store the transmission code to EEPROM o Press SET butto...

Страница 50: ...r and a fan The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions the standard values for them are shown in the table on the right Normal Pressure and...

Страница 51: ...Electric current during operation Low Pressure High Pressure Electric current during operation Insufficient refrigerant gas leakage Clogged capillary tube or Strainer Short circuit in the indoor unit...

Страница 52: ...Display Memorized Error Protective Operation Status 1 Turn power on 2 Press the CHECK button on the remote controller continuously for 5 seconds 3 will be displayed on the remote controller display No...

Страница 53: ...53 17 3 Self Diagnosis Function...

Страница 54: ...54...

Страница 55: ...ransmission is checked whether it is normal Malfunction Caused Faulty indoor unit PCB Faulty outdoor unit PCB Indoor unit outdoor unit signal transmission error due to wrong wiring Indoor unit outdoor...

Страница 56: ...re interconnected Malfunction Caused Wrong models interconnected Wrong indoor unit or outdoor unit PCBs mounted Indoor unit or outdoor unit PCBs defective Indoor outdoor unit signal transmission error...

Страница 57: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Cause...

Страница 58: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors Malfunction Caused F...

Страница 59: ...ons A current transformer CT is detected by checking the compressor running frequency rated frequency and CT detected input current less than 0 65A for continuously 20 seconds Malfunction Caused CT de...

Страница 60: ...termine abnormal fan motor feedback of rotation 2550rpm or 50rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the...

Страница 61: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors Malfunction Caused...

Страница 62: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors Malfunction Caused Faul...

Страница 63: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Fau...

Страница 64: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors Malfunction...

Страница 65: ...lfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused Wrong models interconnected Wrong indoor unit and outdoor unit PCBs...

Страница 66: ...ecision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors Malfunction Caused Fault...

Страница 67: ...ration is used to determine abnormal fan motor Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the fan motor Operati...

Страница 68: ...ture detected by the indoor pipe temperature sensor is above 60 C Malfunction Caused Air short circuit at indoor unit Clogged indoor unit air filter Dust accumulation on the indoor unit heat exchanger...

Страница 69: ...takes place when indoor pipe temperature is lower than 2 C Malfunction Caused Air short circuit at indoor unit Clogged indoor unit air filter Dust accumulation on the indoor unit heat exchanger 2 3 w...

Страница 70: ...nditions When heating operation when indoor pipe temperature is below 10 C When cooling operation when indoor pipe temperature is above 45 C Malfunction Caused Connector in poor contact Faulty sensor...

Страница 71: ...ature and indoor pipe temperature is above 10 C or indoor pipe temperature is below 1 0 C Remark When the indoor standby unit is freezing the outdoor unit transfers F17 error code to the corresponding...

Страница 72: ...eration of cooling and heating when Power Factor Correction PFC protection circuitry at the outdoor unit main PCB senses abnormal high DC voltage level Malfunction Caused DC voltage peak due to power...

Страница 73: ...ality Malfunction Caused Faulty indoor intake air or pipe temperature sensor 2 3 way valve closed Refrigerant shortage refrigerant leakage Clogged expansion valve or strainer Faulty outdoor unit Poor...

Страница 74: ...on Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused Compressor terminal disconnect F...

Страница 75: ...re data 61 C is detected by the outdoor pipe temperature sensor Malfunction Caused Air short circuit at indoor unit Dust accumulation on the indoor unit heat exchanger 2 3 way valve closed Faulty outd...

Страница 76: ...ed o Heat Sink Overheating During operation of cooling and heating when heat sink temperature data 90 C is detected by the heat sink temperature sensor Malfunction Caused IPM overheats due to short ci...

Страница 77: ...ing and heating when compressor tank temperature data 112 C is detected by the compressor tank temperature sensor Malfunction Caused Faulty compressor tank temperature sensor 2 3 way valve closed Refr...

Страница 78: ...n of cooling and heating when an input over current X value in Total Running Current Control is detected by checking the input current value being detected by current transformer CT with the compresso...

Страница 79: ...bleshooting Checking the power transistor Never touch any live parts for at least 10 minutes after turning off the circuit breaker If unavoidable necessary to touch a live part make sure the power tra...

Страница 80: ...Ensure that the capacitor has discharged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 18 1 Indoor Electronic Controllers Cross Flow Fan a...

Страница 81: ...81 Figure 3 Figure 4 18 1 3 To remove discharge grille Figure 5 10 Pull out to remove the drain hose from the discharge grille 11 Then pull the discharge grille downward gently to dismantle it...

Страница 82: ...and indoor fan motor Figure 7 Figure 8 15 Remove the bearing by pulling it out gently 14 Remove the screw from the evaporator 13 Remove the screw that holding the cross flow fan and fan motor axis 12...

Страница 83: ...val of cross flow fan Reminder To reinstall the fan motor adjust the fan motor connector to 45 towards you before fixing control board 17 Remove the cross flow fan from the unit by pulling it to the l...

Страница 84: ...r remove 1 screw 4 Remove the terminal cover remove 2 screws 5 Remove the terminal cover top and disconnect all the lead wires 3 fasten tab inside 18 2 3 Removing the Control Board 6 Remove the contro...

Страница 85: ...cabinet top plate and cabinet front plate 2 Remove the propeller fan by removing the nut turning clockwise at its center 3 Disconnect the connector of the fan motor from the control board 4 Loosen th...

Страница 86: ...86 19 Technical Data 19 1 Operation Characteristics CU 2RE15PBE 19 1 1 One Indoor Unit Operation 19 1 1 1 CS MRE7PKE...

Страница 87: ...87...

Страница 88: ...88 19 1 1 2 CS MRE9PKE...

Страница 89: ...89...

Страница 90: ...90 19 1 2 Two Indoor Unit Operation 19 1 2 1 CS MRE7PKE x2...

Страница 91: ...91...

Страница 92: ...92 19 1 2 2 CS MRE9PKE CS MRE7PKE...

Страница 93: ...93...

Страница 94: ...94 19 2 Operation Characteristics CU 2RE18PBE 19 2 1 One Indoor Unit Operation 19 2 1 1 CS MRE7PKE...

Страница 95: ...95...

Страница 96: ...96 19 2 1 2 CS MRE9PKE...

Страница 97: ...97...

Страница 98: ...98 19 2 1 3 CS MRE12PKE...

Страница 99: ...99...

Страница 100: ...100 19 2 2 Two Indoor Unit Operation 19 2 2 1 CS MRE7PKE x2...

Страница 101: ...101...

Страница 102: ...102 19 2 2 2 CS MRE9PKE x2...

Страница 103: ...103...

Страница 104: ...104 19 2 2 3 CS MRE12PKE x2...

Страница 105: ...105...

Страница 106: ...Exploded View and Replacement Parts List 20 1 Indoor Unit Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service...

Страница 107: ...CO 1 CWH13C1247 26 DISCHARGE GRILLE COMPLETE 1 CWE20C3236 27 BACK COVER CHASSIS 1 CWD933233 28 FULCRUM 1 CWH621131 29 VERTICAL VANE 8 CWE241374 30 CONNECTING BAR 2 CWE261251 33 AIR SWING MOTOR 1 CWA98...

Страница 108: ...108 20 2 Outdoor Unit Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 109: ...MPLETE 4 WAY VALVE 1 CWA43C2585 O 27 SOUND PROOF BOARD 1 CWH151366 29 SENSOR COMPLETE INTAKE PIPE 1 CWA50C2893 O 31 SENSOR COMPLETE GAS 1 CWA50C3070 O 32 SENSOR COMPLETE DEF 1 CWA50C3069 O 33 HOLDER S...

Страница 110: ...CTION 1 CWF615768 65 INSTALLATION INSTRUCTION 1 CWF615769 66 INSTALLATION INSTRUCTION 1 CWF615770 67 INSTALLATION INSTRUCTION 1 CWF615771 68 INSTALLATION INSTRUCTION 1 CWF615772 69 INSTALLATION INSTRU...

Отзывы: