13. Operation and Control
13.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
13.1.1 Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the air conditioner settings and the operation environment.
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the
electrical power is supplied to the unit.
13.1.2 Cooling
Operation
13.1.2.1 Thermostat
control
Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting
temperature < -2.0°C
Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air temperature — Internal setting
temperature > Capability supply OFF point.
13.1.3 Soft Dry Operation
13.1.3.1 Thermostat
control
Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting
temperature < -3.0°C
Capability resume to indoor unit after waiting for 3 minutes, if the Intake Air temperature — Internal setting
temperature > Capability supply OFF point.
13.1.4 Heating
Operation
13.1.4.1 Thermostat
control
Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting
temperature > +1.0°C
During this condition, the indoor fan is stopped if compressor is ON.
Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air Temperature — Internal
setting temperature < Capability supply OFF point.
Содержание CS-MRE7PKE
Страница 15: ...15 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit...
Страница 17: ...17 5 2 Outdoor Unit...
Страница 18: ...18 6 Refrigeration Cycle Diagram...
Страница 19: ...19 7 Block Diagram 7 1 Indoor Unit...
Страница 20: ...20 7 2 Outdoor Unit...
Страница 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 22: ...22 8 2 Outdoor Unit...
Страница 23: ...23 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 24: ...24 9 2 Outdoor Unit...
Страница 26: ...26 10 2 Outdoor Unit...
Страница 53: ...53 17 3 Self Diagnosis Function...
Страница 54: ...54...
Страница 87: ...87...
Страница 88: ...88 19 1 1 2 CS MRE9PKE...
Страница 89: ...89...
Страница 90: ...90 19 1 2 Two Indoor Unit Operation 19 1 2 1 CS MRE7PKE x2...
Страница 91: ...91...
Страница 92: ...92 19 1 2 2 CS MRE9PKE CS MRE7PKE...
Страница 93: ...93...
Страница 94: ...94 19 2 Operation Characteristics CU 2RE18PBE 19 2 1 One Indoor Unit Operation 19 2 1 1 CS MRE7PKE...
Страница 95: ...95...
Страница 96: ...96 19 2 1 2 CS MRE9PKE...
Страница 97: ...97...
Страница 98: ...98 19 2 1 3 CS MRE12PKE...
Страница 99: ...99...
Страница 100: ...100 19 2 2 Two Indoor Unit Operation 19 2 2 1 CS MRE7PKE x2...
Страница 101: ...101...
Страница 102: ...102 19 2 2 2 CS MRE9PKE x2...
Страница 103: ...103...
Страница 104: ...104 19 2 2 3 CS MRE12PKE x2...
Страница 105: ...105...