14.2 Heating Operation
14.2.1 Outdoor fan control
When heating operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted
according to figure below for Heating overload control:
14.2.2 Heating Room Temp Sampling Control
To improve the judgment accuracy, indoor room temperature sampling starts when any indoor unit has stopped
capability supplied (heating thermo-off) during heating operation with compressor ON, outdoor unit will send
signal to all thermo-off indoor units to ON fan motor and get room temperature sample.
To prevent discharge temperature drop at indoor units which is ON when sampling the room temperature of
heating thermo-off units, the compressor frequency is increased accordingly.
However, if indoor room temperature is much higher compare to remote control setting temperature, before
thermo-off, sampling of corresponding indoor unit will be cancelled.
14.2.3 Powerful Operation 2
During cooling / heating operation, this control is to provide fast cooling / heating operation compare to normal
operation.
Operation start if all condition below are complied:
o
Powerful operation ON for indoor unit.
o
Not under Annual Cooling control.
Operation
content:
o
Outdoor fan speed will adjust automatically.
o
Compressor
frequency
will adjust automatically.
Operation stop when comply either one of the follow conditions:
o
When the powerful operation is OFF for all indoor units.
o
When annual cooling control activated.
14.3 Outdoor Quiet Cooling Operation Control
Purpose
Provide quiet cooling operation when only 1 indoor in operation.
Start
Condition
o
Indoor fan speed is lower than Lo fan.
o
Only 1 operation indoor unit.
o
Not in any cooling overload zone.
o
Not during annual cooling
o
Not initial frequency operation.
o
Not during starting control.
o
Not during “Electronic part temperature rise protection by outdoor air & total current”
o
Not during “Electronic part temperature rise protection by total current”
o
Not during “IPM temperature rise prevention control”
o
During
cool
mode
All conditions above are satisfied and function selection enable.
Содержание CS-MRE7PKE
Страница 15: ...15 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit...
Страница 17: ...17 5 2 Outdoor Unit...
Страница 18: ...18 6 Refrigeration Cycle Diagram...
Страница 19: ...19 7 Block Diagram 7 1 Indoor Unit...
Страница 20: ...20 7 2 Outdoor Unit...
Страница 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 22: ...22 8 2 Outdoor Unit...
Страница 23: ...23 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 24: ...24 9 2 Outdoor Unit...
Страница 26: ...26 10 2 Outdoor Unit...
Страница 53: ...53 17 3 Self Diagnosis Function...
Страница 54: ...54...
Страница 87: ...87...
Страница 88: ...88 19 1 1 2 CS MRE9PKE...
Страница 89: ...89...
Страница 90: ...90 19 1 2 Two Indoor Unit Operation 19 1 2 1 CS MRE7PKE x2...
Страница 91: ...91...
Страница 92: ...92 19 1 2 2 CS MRE9PKE CS MRE7PKE...
Страница 93: ...93...
Страница 94: ...94 19 2 Operation Characteristics CU 2RE18PBE 19 2 1 One Indoor Unit Operation 19 2 1 1 CS MRE7PKE...
Страница 95: ...95...
Страница 96: ...96 19 2 1 2 CS MRE9PKE...
Страница 97: ...97...
Страница 98: ...98 19 2 1 3 CS MRE12PKE...
Страница 99: ...99...
Страница 100: ...100 19 2 2 Two Indoor Unit Operation 19 2 2 1 CS MRE7PKE x2...
Страница 101: ...101...
Страница 102: ...102 19 2 2 2 CS MRE9PKE x2...
Страница 103: ...103...
Страница 104: ...104 19 2 2 3 CS MRE12PKE x2...
Страница 105: ...105...