Safety precautions

27

English

Installation instruction (Safety precautions)

SAFETY PRECAUTIONS

•    Read the following “SAFETY PRECAUTIONS” carefully before installation.

•    Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug 

      and main circuit for the model to be installed.

•    Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is 

     classified by the following indications.

Do not install the unit in a place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.

Prevent liquid or vapor from entering sumps or sewers since vapor is heavier than air and may form suffocating atmospheres.

Do not release refrigerant during piping work for installation, re-installation and during repairing refrigeration parts. Take care of the liquid refrigerant, it may cause

frostbite.

Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

Do not touch the sharp aluminium fin, sharp parts may cause injury.

Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.

Select an installation location which is easy for maintenance. Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may

result in loss damage or injury and/or property.

Power supply connection to the room air conditioner.

Use power supply cord 3 x 1.5 mm² (1.5 ~ 2.0HP), 3 x 2.5 mm² (2.5HP) type designation ISO 694 or 60245 IEC 57 or heavier cord. 

Connect the power supply cord of the air conditioner to the mains using one of the following method.

Power supply point should be in easily accessible place for power disconnection in case of emergency.

In some countries, permanent connection of this air conditioner to the power supply is prohibited.

Installation work. It may need two people to carry out the installation work.

Keep any required ventilation openings clear of obstruction.

1) Power supply connection to the receptacle using power plug.

     Use an approved 15/16A (1.0 ~ 1.5HP) or 16A (2.0HP) or 20A (2.5HP) power plug with earth pin for the connection to the socket.

2) Power supply connection to a circuit breaker for the permanent connection.

     Use an approved 16A (1.0 ~ 2.0HP) or 20A (2.5HP) circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0 mm contact gap. 



 

CAUTION

 •








 

Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and cross

over the handrail causing an accident.

Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.

Do not sit or step on the unit, you may fall down accidentally.

Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.

When installing or relocating air conditioner, do not let any substance other than the specified refrigerant, eg. air etc mix

into refrigeration cycle (piping). Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc. 

Do not add or replace refrigerant other than specified type. It may cause product damage, burst and injury etc.

Do not perform flare connection inside a building or dwelling or room, when joining the heat exchanger of indoor unit with interconnecting piping. Refrigerant 

connection inside a building or dwelling or room must be made by brazing orwelding. Joint connection of indoor unit by flaring  method can only be made at outdoor 

or at outside of a buidling or dwelling or room. Flare connection may cause gas leak and flammable atmospheres.

 

For R32/R410A model, use piping, fl

are nut and tools which is speci

 ed for R32/R410A refrigerant. Using of existing (R22) piping, 

 are nut and tools may cause

abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury. For R32 and R410A, the same flare nut on the outdoor unit 

side and pipe can be used.

Since the working pressure for R32/R410A is higher than that of refrigerant R22 model, replacing conventional piping and flare nuts on the outdoor unit side are

recommended. 

If reuse piping is unavoidable, refer to instruction “IN CASE OF REUSING EXISTING REFRIGERANT PIPING” 

Thickness of copper pipes used with R32/R410A must be more than 0.6 mm. Never use copper pipes thinner than 0.5 mm.

It is desirable that the amount of residual oil less than 40 mg/10 m.

Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fire.

For refrigeration system work, install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fire.

Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fi

 re or electrical shock.

Install at a strong and 

 rm location which is able to withstand weight of the set. If the strength is not enough or installation is not properly done, the set will drop and 

cause injury.

For electrical work, follow the national regulation, legislation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit

capacity is not enough or defect found in the electrical work, it will cause electrical shock or fire.

Do not use joint cable for indoor / outdoor connection cable. Use the specified indoor/outdoor connection cable, refer to instruction     

CONNECT THE CABLE TO 

THE INDOOR UNIT 

and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection or 

fixing is not perfect, it will cause heat up or fi

 re at the connection.

Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fi

 

xed perfectly, it will cause fire or electrical shock.

This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD), with sensitivity of 30mA at 

0.1 sec or less. Otherwise, it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown.

During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fixing refrigeration piping and valves at 

opened position will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.

During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves 

are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.

Tighten the flare nut with torque wrench according to specifi

 ed method. If the 

 are nut is over-tightened, after a long period, the 

 are may break and cause refrigerant

gas leakage.

After completion of installation, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts with fire.

Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.

Be aware that refrigerants may not contain an odour.

 
 

 

WARNING

Содержание CS/CU-KU12ZKY Series

Страница 1: ...n the installer should Read the Installation Operating Instructions then request the customer keep them for future reference Remove the remote control packed with the indoor unit Air conditioner Opera...

Страница 2: ...and COOL mode 16 C 30 C Operating the unit within the recommended temperature range may save energy HEAT 20 C 24 C COOL 26 C 28 C Default set temperature is 24 C in COOL mode as per country guidelines...

Страница 3: ...E POWERFUL AIR SWING FAN SPEED SLEEP TEMP CLEAN TIMER ON OFF CLOCK LOCK CANCEL ECO converti7 SMART AIR CONDITIONER FAN CHECK MODE POWERFUL AIR SWING FAN SPEED SLEEP TEMP CLEAN TIMER ON OFF CLOCK LOCK...

Страница 4: ...of a leak Please consult authorised dealer or specialist to clean the internal parts repair install remove and reinstall the unit Improper installation and handing will cause leakage electric shock o...

Страница 5: ...e the same as conventional refrigerant R410A R22 models Since the working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Espec...

Страница 6: ...accredited assessment authority which authorizes their competence to handle refrigerants safely in accordance with an industry recognised assessment specification Servicing shall only be performed as...

Страница 7: ...where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being co...

Страница 8: ...nd during the brazing process 8 Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important...

Страница 9: ...hat it has been de commissioned and emptied of refrigerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 12 Rec...

Страница 10: ...er every 3 hours operation Press hold for 5 seconds to turn ON OFF the hidden display Press for 5 seconds to lock unlock remote keypad When keypad is locked remote display will show LO when any button...

Страница 11: ...in to increase timer time in step of 10 minutes or CL will be displayed on unit and remote controller CL on unit display is not applicable for LU Models While CL is displayed all other functions of th...

Страница 12: ...be upto 70 Step 6 55 is display on Unit and Remote Unit Input Power will be upto 55 Step 7 40 is display on Unit and Remote Unit Input Power will be upto 40 Press converti7 button again to exit from...

Страница 13: ...the filter surface Dry the dust filters thoroughly under shade away from fire or direct sunlight Replace any damaged filters Ag Clean Filter PM0 1 filter Clean the filter whenever necessary Don t was...

Страница 14: ...some alpha numeric codes appear on IDU display Unit s Wi Fi connection with the router is activated Wi Fi LED stays ON during unit turn OFF Check unit s Wi Fi connection with router Wi Fi LED continu...

Страница 15: ...15 Troubleshooting Notes...

Страница 16: ...ted There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not place any obstacles whic...

Страница 17: ...as leaks and secure with vinyl tape Vinyl tape Insulation of piping connections Remote control holder Remote control holder xing screws Remote control Attaching the remote control holder to the wall 5...

Страница 18: ...this line 1 Mount the installation plate on the wall with 5 screws or more at least 5 screws If mounting the unit on the concrete wall consider using anchor bolts Always mount the installation plate...

Страница 19: ...left piping Right Rear piping Cover for piping How to keep the cover In case of the cover is cut keep the cover at the rear of chassis as shown in the illustration for future reinstallation Left right...

Страница 20: ...m m Connection cable Gas side piping Liquid side piping Drain hose Insert the connection cable This can be used for left rear piping and bottom piping also How to pull the piping and drain hose out i...

Страница 21: ...roprene sheathed 4 x 1 0 mm2 1 5 1 8HP 4 x 1 5 mm2 2 0HP or 4 x 2 5mm2 2 5HP exible cord type designation IS 694 or 60245 IEC 57 or heavier cord Bind all the indoor and outdoor connection cable with t...

Страница 22: ...n this area must follow to national wiring rules Do not joint wires Wire stripping No loose strand when inserted 10 1 mm Conductor fully inserted ACCEPT Conductor over inserted PROHIBITED Conductor no...

Страница 23: ...e speci ed torque as stated in the table Do not overtighten overtightening may cause gas leakage Piping size Torque 6 35 mm 1 4 18 N m 1 8 kgf m 9 52 mm 3 8 42 N m 4 3 kgf m 12 7 mm 1 2 55 N m 5 6 kgf...

Страница 24: ...unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1 0 mm2 1 5 1 8HP 4 x 1 5 mm2 2 0HP or 4 x 2 5mm2 2 5HP exible cord type designation IS 694 or 60245 IEC 57 or heavier cord Do not...

Страница 25: ...aps 1 5 2 0HP or 3 caps 2 0 2 5HP on the front grille as shown in the illustration at top and then remove the 4 mounting screws 3 Pull the lower section of the front grille towards you to remove the f...

Страница 26: ...insulating material with a new one Heat insulating material is required for both liquid side and gas side piping Most Important Process Purpose To make the oil refrigerant mix together They are in se...

Страница 27: ...oint connection of indoor unit by aring method can only be made at outdoor or at outside of a buidling or dwelling or room Flare connection may cause gas leak and ammable atmospheres For R32 R410A mod...

Страница 28: ...e for Full Load 100 and Half Load 50 1 Mode Select COOL 2 Temperature a 16 C for Full Load 100 3 Air Swing S 4 Fan speed et vane position to 3rd step from top b 17 C for Half Load 50 For Full Load For...

Страница 29: ...top For COOL Mode This test guideline is applicable for KZ models only FULL LOAD HALF LOAD FULL LOAD HALF LOAD QUIET CLEAN Open the Front Panel by lifting Intake Grille Follow the below Instructions 4...

Страница 30: ...ranty for 3 years from the date of purchase Product ROOM AIR CONDITIONER Panasonic Life Solutions India Pvt Ltd Model No ODU SI No IDU SI No Customer Name Address Tel No Date of Purchase Invoice No De...

Страница 31: ...re eg Rat lizard insect ants etc inside the Product unit f Use of harmful chemicals Improper heat load Usage of unit in an abnormally corrosive alkaline acidic atmosphere g Any change or defect result...

Страница 32: ...m in corporate sustainability panasonic india i recycle program html S No 1 All electrical and electronic products are required to be handed over only to the Authorized recycler 2 The product should b...

Отзывы: