ZENIT
80
+
TYPE TUBE RADIANT HEATER
Instructions for Installation and Servicing
28
Modulation control
There are three states according to operation of appliance: Out off operation, operation between performance of 100% and 50% or ma
-
ximum (100%) performance. Is the control of appliance by the thermostat which can sense the room temperature. The thermostat can
control the black tube radiant heater according to needed set up temperature. (The detailed manual of thermostat can be found suppli-
ed with thermostat) When the thermostat send a sign than the heater starts with maximum performance (this time is minimum 30 sec)
The appliance keeps this performance till the difference is between temperature of room and the setted temperature is 3°C degrees,
than the control begin degrease the performance of appliance without any stage continuously to 50% of performance where the control
keeps it during this time till the temperature reaches the setted temperature. After these the thermostat sut off the appliance. Type of
thermostat can be: only use capable type of control which can handle the modulation control.(e.g.: FP-MOD type by Pakole Trade Kft.)
The connection diagram could change anytime: so we recomend to use the digaram which was attea-
ched to the appliance.
electrical connection
FU
SE
NM
VeL
N
L1
LT
VL
VN
SL
V.1
5-1
C
FAN
VL
VN
SL
PE
12 11 10 9
8
7
6
5
4
3
2
1
SIT 579 DBC
APS
14
13
Green
Red
Pici Hirschmann
845 SIGMA
Segéd
szelep
L1
MN
N
The circuit of ZENIT tube radiant heater appliance with modulation regulation
with SIT electronics/ with SIT solenoid valve/ with HIRSCHMANN plug
Slave valve
Hirschmann
12.picture: modulation regulation electrical connection of ZENIT appliance with SIT control box