Model:
ZENIT 80+ 15m „L”
Gas-fired overhead radiant tube heaters Linear shape
Type of heating:
Radiant tube
Fuel:
Gaseous
Type of fuel:
Natural Gas
Propane
Butane
Propane-Butane
Space heating emmission NO
x
141,1
mg/kWh
input
(GCV)
Characteristics when operating with the preffered fuel only
Item
Symbol Value
Unit
Item
Symbol Value
Unit
Heat output
Useful efficiency - GCV
Nominal
heat output
P
nom
43,9
kW
Useful efficiency at nominal
heat output
h
th,nom
82,30
%
Minimum
heat output
P
min
26,7
kW
Useful efficiency at minimum
heat output
h
th,min
81,20
%
Minimum heat
output -
as percentage
of nominal heat output
--
60,7
%
Radiant factor
Envelop losses
Radiant factor at
nominal
heat output
RF
nom
66,9
%
Envelope insulation class
U
0,0
W/m
2
K
Radiant factor at
minimum
heat output
RF
min
64,5
%
Envelope loss factor
F
env
0,0
%
Heat generator to be installed
outside the heated area
Yes
No
Possible
Auxiliary electricity consumption
Heat output controll type
At Nominal heat
output
el
max
0,10
kW
- Singl stage (ON-OFF)
Yes
No
At minimum heat
output
el
min
0,06
kW
- Two stage (100%-60%-OFF)
Yes
No
In standby
mode
el
sb
0,0
kW
- Modulated
Yes
No
Permanent pilot flame power requirement
Pilot flame pow-
er requirement
(if applicable)
P
pilot
0,0
kW
Contact
details
PAKOLE Trade Kft. H-8000, Székesfehérvár, Börgöndi út, 8-10