Signals test
1. Apply an enable input to the drive. The green ENABLE
LED should be On. If the LED is not On, check for a
valid DIP switch code per section 2.6.1, Step Set Up. If
not, refer to section 3.2.2.
2. Verify that the motor has holding torque by attempting to
rotate the motor shaft. The energized motor shaft is
either immovable or very resistant to rotation when the
5630 is enabled.
3. Input a step command and verify that the motor moves.
Note: Do not change the direction input within 1
millisecond before or after the step input goes high.
4. Input a direction signal and step the motor. The direction
of rotation should change.
5. Continue exercising the unit, testing it in your application.
Getting help
If you need further help with your installation contact Pacific
Scientific at 815-226-3100 from 8 am to 5 pm Eastern
Standard Time, or contact your Pacific Scientific distributor.
Rev E
5630 Installation and Hardware Reference Manual
3 - 3