![Pacific Power Source UPC-3 Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/pacific-power-source/upc-3/upc-3_operation-manual_3150600021.webp)
SECTION 2
SPECIFICATIONS
9
2.1.2.1 CSC (CONTINUOUS SELF CALIBRATION)
SPECIFICATIONS
CSC capability is not available in the Manual versions of the controller (UPC-3M and UPC-1M)
The UPC includes a user selectable “Continuous Self Calibration” function. When active, this function
maintains a constant output voltage amplitude at the metering sense point, comparing the metered
voltage at that point to the set value and correcting for any difference. Accurate calibration of the voltage
metering function is essential for CSC to operate accurately.
When INT SENSE is chosen, CSC attempts to precisely maintain accurate COMMAND (program)
voltage at the input side of the Output Relay of the power source.
To compensate for load voltage drops due to distribution losses, CSC can be effectively used to maintain
COMMAND (program) voltage very precisely at the load by selecting EXT sense with sense leads
connected at the load and having CSC enabled.
Basic properties of the CSC function are:
1.
Voltage level held to
±
0.05% of the program voltage referenced to the internal voltmeter with
CSC enabled.
2.
Response time varies anywhere from 100 mSec. to 200 mSec. and only responds while the
UPC is metering, not while in Program Edit or Setup mode.
3.
CSC operates independently of selected waveform, does not increase distortion and is stable
into any PF load.
4.
Automatically switches between internal and remote voltage sensing as the metering function is
switched between INT and EXT.
5.
CSC does NOT function during Transients or Transition Time.
6.
CSC will only correct the Output Voltage by ± 10%. If the sense voltage is not within ± 10% of the
COMMAND voltage, CSC will become disabled until the Output Voltage is back within ± 10% of
the COMMAND voltage. Each phase operates independently.
2.1.3 CURRENT LIMIT CONTROL SPECIFICATIONS
Current Limit is not available in the Manual versions of the controller (UPC-3M and UPC-1M)
Current limit is provided for all phases through a single RMS current value. The range of this value is
equal to the ammeter range, as set by the AMPS TO VOLTS RATIO (see 2.2.2). This function is an
average responding, RMS programmed function, with a response time of approx. 50 mSec.
Range:
Amps to Volts Ratio x 10 (divide by 3 for 3
Φ
power form)
(divide by 1.5 for single phase power sources containing 2 power amps).
Resolution: Range/2000
(.05%).
Accuracy:
±3
% of full scale over the full range of ambient conditions.
Содержание UPC-3
Страница 1: ...UPC 3 UPC 1 PROGRAMMABLE CONTROLLERS FIRMWARE V4 25 AND LATER OPERATION MANUAL PACIFIC POWER SOURCE δ ...
Страница 2: ......
Страница 12: ...SECTION 1 GENERAL viii THIS PAGE INTENTIONALLY BLANK ...
Страница 17: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 3 Figure 1 3b UPC 3 Figure 1 3c UPC 1 ...
Страница 43: ...SECTION 4 OPERATION 31 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL ...
Страница 74: ...SECTION 4 OPERATION 62 90 0 100 0 85 95 100 90 FIGURE 4 6 2 1 EDITED WAVEFORM ...
Страница 134: ...NOTES 122 NOTES ...
Страница 135: ...MODIFCATIONS 123 MODIFICATIONS MODIFICATIONS This section is reserved for any modifications that may be made ...