The Fiber OWL 4 should read approximately -10.00 dBm. If the reading is below -11.00 dBm, the patch cable should be
replaced.
Once proper operation has been verified, remove the first patch cable from both units and set it aside.
Connect the second singlemode patch cable between the Fiber OWL 4 and the WaveSource as shown in Figure 2.
The Fiber OWL 4 should read approximately -10.00 dBm. If the reading is below -11.00 dBm, the patch cable should be
replaced.
Once proper operation has been verified, press
to return to the OPERATING MODE menu.
RUN LINK WIZARD
From the OPERATING MODE menu, press
to highlight CERTIFICATION METER, then press
to SELECT.
From the START MENU, press
to start the LINK WIZARD.
From the STORED LINKS menu, press
to highlight the stored link name you wish to use and
press
to SELECT.
OPTIONAL:
you may change the link name to something that better describes the group of fibers
you are testing. Enter the new name for the link, then press
to continue.
Change the LINK DATE to the date of test using the format
MM-DD-YY
, then press
.
Press
to highlight the fiber optic cabling standard, then press
to SELECT.
Press
to highlight the fiber type of the network under test, then press
to SELECT.
Press
to measure the fiber length with the Fiber OWL 4 BOLT. If you wish to enter the length
manually, press
and skip to
.
The date of test must be set so that the correct date appears on certification reports.
If unsure about which cabling standard to use, select TIA-568-B.3.
DONE
F1
F2
1
ABC
F1
F2
DONE
DONE
F1
F2
F1
F2
1
ABC
F2
QUICK REFERENCE GUIDES
PAGE 2 OF 5
<1>LINK WIZARD
<2>MAIN MENU
START MENU
Fiber Link 2
NEXT
SELECT
Fiber Link 3
Fiber Link 4
STORED LINKS
_____________________
Fiber Link 1
<---
SHIFT
--->
[Fiber Link 1
]
LINK NAME:
_____________________
USER DEFINED #1
USER DEFINED #2
NEXT
SELECT
ISO/IEC 11801
FIBER STANDARDS
_____________________
TIA-568B 3/CAN-T529
50 0um MultiMode
NEXT
SELECT
OUTDOOR SingleMode
FIBER TYPES
_____________________
INDOOR SingleMode
62 5um MultiMode
<1> USE THE METER TO
MEASURE LENGTH
<2> ENTER LENGTH
FIBER LENGTH METHOD
MANUALLY
Optical Power Meter:
Fiber OWL 4
Fiber Optic Light Source:
WAVESOURCE Series Singlemode Sources
<---
SHIFT
--->
[03-20-08]
DATE: [MM/DD/YY]
_____________________