TAKE READINGS
Disconnect the mandrel-wrapped patch cable from the Fiber OWL 4 and take the units to opposite ends of the link.
Connect the units to the first fiber to test as shown in Figure 6. Your readings will vary from the example below.
Press
to store the data point. If this is the first data point in the link, you may be prompted to enter a new label.
Press
to save the data point.
Disconnect the patch cables from the patch panels and move them to the next port in the patch panel, then repeat steps
through
until all fibers in the link have been tested at 850nm.
If also testing at 1300nm, repeat steps
through
, but this time use the mandrel-wrapped patch cable attached to
the 1300nm port. Also, make sure that you set the Fiber OWL 4 and the Dual OWL to 1300nm.
Do NOT disconnect the patch cable(s) from the light source at any time until all fibers have been tested.