6
Suitable measures (e.g. safety valves) have to be
taken to ensure that the maximum operating pres-
sures and maximum and minimum operating tem-
perature are not exceeded or undercut.
Heavy control station!
Risk of injury!
Suitable transport and lifting devices
are to be used. Wear suitable protective clothing
(e.g. safety shoes) during installation and use safety
devices. External components like handwheels or
pressure test points must not be misused for the
absorption of external forces, e.g. as connection
point for lever tools etc.
Hot and cold surfaces!
Risk of injury!
Only touch with safety gloves. The
control station can get very hot during operation.
Sharp edges!
Risk of injury!
Only touch with safety gloves. Thre-
ads, bore holes and edges are sharp.
Small components!
Risk of ingestion!
Store and install control station
out of reach of children.
Allergies!
Health hazard!
Do not touch the control station
and avoid any contact if allergies against the used
materials are known.
3 Transport, storage and
packaging
3.1 Transport inspection
Upon receipt check delivery for any damages caused
during transit.
Any damage must be reported immediately upon re-
ceipt.
3.2 Storage
The control station “Regufloor H” must only be stored
under the following conditions:
– Do not store in open air, but dry and free from dust.
– Do not expose to aggressive fluids or heat sources.
– Protect the control station from direct sunlight and
mechanical agitation.
– Storage temperature: –20°C up to +60°C,
max. relative humidity of air: 95 %
3.3 Packaging
Packaging material is to be disposed of environmen-
tally friendly.
4 Technical data
4.1 Performance data
Control station
Max. operating pressure p
s
: 6 bar
Max. differential pressure:
0,75 bar
Max. operating temperature
t
s
primary side:
90˚ C
Max. operating temperature
t
s
secondary side:
50˚ C
Setting range of controller: 20-50˚ C
Electric sensor attachment to pipe
Temperature range:
20-90˚ C
k
vs
-value:
4 m
3
/h
Performance range:
up to 15 kW or a heating
surface up to 200m² with
a heat demand of 75 W/m²
Pump:
Technical data of the pump is detailed in separate
operating instructions.
Fluid:
Non-aggressive fluids (e.g. water and suitable
water and glycol mixtures according to VDI 2035). Not
suitable for steam, oily and aggressive fluids.
2 Safety notes
2.1 Correct use
Safety in operation is only guaranteed if the control
station is used correctly.
The control station “Regufloor H” locally controls the
flow temperature of surface heating systems.
Any use of the control station outside the above ap-
plications will be considered as non-compliant and
misuse. Claims of any kind against the manufacturer
and/or his authorised representatives due to damages
caused by incorrect use cannot be accepted.
The observance of the installation and operating in-
structions is part of the compliance terms.
2.2 Possible dangers at the installation location
and during transport
The case of an external fire has not been taken into
consideration when constructing the control station.
WARNING
!
DANGER
!