PRO208V-5k75 Installation and Safety Manual
900-0203-01-00 Rev B
16
(b)
Mate the male and female AC
connector to connect the inverter to the
AC system.
Use the AC tool to disconnect the male
and female connectors. Follow steps 1
through 3 in the Disconnection section
of Figure 11.
3.
Connect the Communications Gateway.
CAUTION: Hazard to Equipment
The Gateway Device is rated for indoor installation only.
(a)
The Gateway should be
located indoors
, as near to the inverter(s) as possible for reliable
communications. See Figure 12.
Figure 12: Wiring of the Communications Gateway
Up to 3
inverters
on single 60A
OCPD
ProHarvest 208V
inverter
Means of
AC disconnect
Means of DC
disconnect
Equipment
ground
Gateway
Gateway 120 Vac cable
(sold separately)
CBL-GW120A-6
Additional dedicated
branch circuits
Dedicated
branch circuit
1 phase
(15A OCPD)
Neutral
Ground
Load Center
OCPDs
208 Vac
3-phase
source
3 phases
Neutral
Ground
Inverter AC cable
(sold separately)
Figure 11: Connecting and disconnecting of the
inverter AC connection
Connection
3
1
Disconnection
AC Tool
1
2
3