Operation
46
900-0145-01-01 Rev A
Table 5
Aux Mode Functions
Name
Purpose
Triggers
Settable
Points
Start
Stop
Load
Shed
Operates designated loads
normally; turns off loads in
severe conditions
High Vdc
Low Vdc
High temp
Low output Vac
High input Aac
Low & high Vdc
On & Off delay
Gen Alert
Starts generator to charge
batteries
Low Vdc
High Vdc
Low & high Vdc
On & Off delay
Fault
Signals that the Radian shut
down due to error
Error present
Error cleared
None
Vent Fan
Runs fan to vent batteries
while charging
High Vdc
Below high Vdc
High Vdc
Off delay
Cool Fan
Runs fan to cool Radian
Internal sensor > 60°C
Internal sensor < 49°C None
DC Divert
Turns on DC dump load to
prevent overcharging
High Vdc
Low Vdc
Low & high Vdc
On & Off delay
GT Limits
Signals disconnect of grid-tied
Radian due to AC conditions
GIP parameters not
met
GIP parameters met
None
Source
Status
Signals that the Radian
accepted an AC source
AC source accepted
AC source
disconnected
None
AC Divert
Turns on AC dump load to
prevent overcharging
High Vdc
AC source accepted
Low Vdc
High output load
High temp
Low & high Vdc
On & Off delay
NOTES:
Содержание GS3548E
Страница 1: ...Radian Series Inverter Charger GS7048E GS3548E Operator s Manual...
Страница 6: ...Table of Contents 4 900 0145 01 01 Rev A This page intentionally left blank...
Страница 64: ...Troubleshooting 62 900 0145 01 01 Rev A NOTES...
Страница 75: ...Index 900 0145 01 01 Rev A 73 V Vent Fan Control 44 W Warning Symbol 5 Warnings 58 Website 12 67...