Operation
22
900-0145-01-01 Rev A
Description of Inverter Operations
The items in this section are operations common to all Radian inverters. These are used in most or all
of the input modes described in the preceding section.
Some of the items in this section are functions which can be manually selected, enabled, or
customized. Other items are general topics or applications for the inverter. These items may not have
their own menus, but their activity can still be influenced or optimized by changing certain settings.
Any of these items may need to be adjusted so that the inverter is best matched to a particular
application. The operator should review these items to see which are applicable.
All items described as settable or adjustable have set points which can be accessed using the
system display. The default settings and ranges of adjustment are listed in Table 16 beginning on
page 67 of this manual.
Inverting
This is the Radian inverter’s primary task. The inverter converts DC voltage from batteries into AC
voltage that is usable by AC appliances. It will continue to do this as long as the batteries have
sufficient energy. The batteries can be supplied or recharged from other sources, such as solar, wind,
or hydroelectric power.
The inverter’s design uses transformers and high-frequency H-Bridge FET modules to achieve the
required high-wattage output. In the GS7048E, the dual design allows half the inverter to shut down
for lower idle consumption when not in use.
The Radian can deliver the rated wattage continuously at 25°C. The maximum output is derated at
temperatures exceeding 25°C. See pages 63 and 65 for these wattages.
Measure the total load wattage so that it does not exceed the Radian’s capacity. The Radian cannot
maintain its AC voltage under an excessive load. It will shut down with a
Low Output Voltage
error.
DC and AC Voltages
The Radian inverter requires batteries to operate
. Other sources may not maintain DC voltages
that are consistent enough for the inverter to operate reliably.
CAUTION: Equipment Damage
Do not substitute other DC sources in place of the batteries. High or irregular
voltages may damage the inverter. It is normal to use other DC sources with
the batteries and the inverter, but not in place of the batteries.
The following items will affect the inverter’s operation. These are only used when the inverter is
generating AC power on its own.
Low Battery Cut-Out
: This function prevents the inverter from draining the batteries completely. When the
DC voltage drops below a specified level for 5 minutes, the inverter will stop functioning. The MATE3 will
give a
Low Battery V
error. This is one of the error messages described on page 57. It appears as an event
on the MATE3 system display
.
This function is intended to protect both the batteries and the inverter’s output. (Continuing to invert on a
low DC voltage may produce a distorted waveform.) This item is adjustable.
V
V
Содержание GS3548E
Страница 1: ...Radian Series Inverter Charger GS7048E GS3548E Operator s Manual...
Страница 6: ...Table of Contents 4 900 0145 01 01 Rev A This page intentionally left blank...
Страница 64: ...Troubleshooting 62 900 0145 01 01 Rev A NOTES...
Страница 75: ...Index 900 0145 01 01 Rev A 73 V Vent Fan Control 44 W Warning Symbol 5 Warnings 58 Website 12 67...