Specifications
900-0145-01-01 Rev A
67
Firmware Revision
This manual applies to inverter models GS7048E and GS3548E with Revision 001.005.xxx or higher.
Updates to the Radian’s firmware are periodically available. These can be downloaded from the
OutBack website
www.outbackpower.com
. See page 12.
Default Settings and Ranges
NOTE:
Some items are retained at the present setting even when the inverter is reset to factory
defaults. These items are noted with the letter “X” in the Item column.
Certain items, particularly those in the Auxiliary menus, share common set points. If one of these
items is changed in a mode menu, the change will appear in other menus that use the same set point
Certain menus are only visible when the installer password is used, particularly the Grid Interface
Protection menu. These menus are bordered in the table with a double line of this style:
Table 16
Radian Inverter Settings
Field
Item
Default
Minimum
Maximum
INVERTER
Hot Key Inverter Mode
Off
On
,
Off
, or
Search
CHARGER
Hot Key Charger Control
On
On
or
Off
AC Input
Hot Key
AC Input Mode
Use
Drop
or
Use
Search
Sensitivity
(see page 23 for increments)
10
0
250
Pulse Length
8 AC Cycles
4 AC Cycles
20 AC Cycles
Pulse Spacing
60 AC Cycles
4 AC Cycles
120 AC Cycles
AC Input and
Current Limit
Input Priority
Grid
Grid
or
Gen
Grid Input AC Limit
50 Aac
5 Aac
55 Aac
Gen Input AC Limit
50 Aac
5 Aac
55 Aac
Charger AC Limit
GS7048E
30 Aac
0 Aac
30 Aac
GS3548E
15 Aac
0 Aac
15 Aac
Grid AC Input
Mode and Limits
Input Mode
Grid Tied
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit Lower
208 Vac
170 Vac
230 Vac
(Voltage Limit)
Upper
252 Vac
232 Vac
290 Vac
Transfer Delay
1 second
0.12 seconds
4.0 seconds
Connect Delay
0.2 minutes
0.2 minutes
25.0 minutes
When
Mini Grid
mode is selected:
Connect to Grid
48.0 Vdc
44.0 Vdc
64.0 Vdc
(Connect)
Delay
10 minutes
2 minutes
200 minutes
When
Grid Zero
mode is selected:
DoD Volts
48.0 Vdc
44.0 Vdc
64.0 Vdc
DoD
Amps
GS7048E
5 Aac
1 Aac
30 Aac
GS3548E
5 Aac
1 Aac
15 Aac
Gen AC Input
Mode and Limits
Input Mode
Generator
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit Lower
208 Vac
170 Vac
230 Vac
(Voltage Limit)
Upper
252 Vac
232 Vac
290 Vac
Transfer Delay
1 second
0.12 seconds
4.0 seconds
Connect Delay
0.5 minutes
0.2 minutes
25.0 minutes
If
Mini Grid
mode
is selected:
Connect to Grid
48.0 Vdc
44.0 Vdc
64.0 Vdc
(Connect)
Delay
10 minutes
2 minutes
200 minutes
If
Grid Zero
mode
is selected:
DoD Volts
48.0 Vdc
44.0 Vdc
64.0 Vdc
DoD
Amps
GS7048E
5 Aac
1 Aac
30 Aac
GS3548E
5 Aac
1 Aac
15 Aac
Содержание GS3548E
Страница 1: ...Radian Series Inverter Charger GS7048E GS3548E Operator s Manual...
Страница 6: ...Table of Contents 4 900 0145 01 01 Rev A This page intentionally left blank...
Страница 64: ...Troubleshooting 62 900 0145 01 01 Rev A NOTES...
Страница 75: ...Index 900 0145 01 01 Rev A 73 V Vent Fan Control 44 W Warning Symbol 5 Warnings 58 Website 12 67...