EH-105
Press the
button to browse. The list shows for which
use the measurement channels and digital inputs have
been reserved.
”-” indicates that the control command is activated but the
control has no influence at the moment.
Connection information is primarily intended for the maintenance person. It shows
what the measurement channels and digital inputs have been reserved for and
which ones are still free. Channels 1-6 are primarily intended for NTC
measurements. Channels 7-11 are primarily intended for transmitter measurements,
but they can also be connected to On/Off inputs. Channels 21-27 can only be
connected to On/Off inputs. (see pages 43-45).
Select
Measurements
AHU oper.contr.
Settings
Supply air info
AHU output info
Connection info
AHU 1/1 Autom.
Room temp.21.2
SupplyTemp20.4
Selection
°C
°C
Measurements and On/Off inputs are individually outlined
in the operating instructions on pages 44-45.
12
Connection info
1= Outdoor temp
2= Supply temp
3= Exhaust temp
4= Return water
5= SupplyAft.HRU
6=-
7= HRU frostPDE
8= SF press
9= EF press
10=SF filterPDE
11=EF filterPDE
21=
SF 1/1 run
22=
SF 1/2 run
23=
EF 1/1 run
24= GenAlClose
25=-
26=-
27=-
C
C
C
AH OUTPUT INFORMATION /
CONNECTION INFORMATION
Connection point of measurement or On/Off input on the
controller's strip connector.
CONNECTION INFORMATION
AHU output info%
Week clock
100
CO2 enhance
80
HeatEnhance
-
OutdT Limit
65
The AH output info display shows all the currently activated control commands.
The
character is at the determining (strongest) factor. The numeral indicates the
amount of the AH unit output control. AH priorities are illustrated on page 8.
AH OUTPUT INFORMATION
"- " Character indicates that the
control command is in use but
control has no effect at this moment.
Commanding (strongest) factor
Select
Measurements
AHU oper.contr.
Settings
Supply air info
AHU output info
Connection info
AHU 1/1 Autom.
Room temp.21.2
SupplyTemp20.4
Selection
°C
°C