EH-105
CASCADE CONTROL SYSTEM
EH-105
CascadeCtrlSyst
DamperMin-Heat
Heat-DamperMin
The order in which heating and dampers function is selected in the cascade
control system when there is a need to increase the room temperature.
Dampers
Heating
Minimum limit
during heating
Phase 1
Phase 2
Dampers
open
closed
open
closed
Heating
Phase 1
Phase 2
DamperMin-Heat:
Heat-DamperMin:
When the temperature must be increased, the
heating output is first increased. When heating has reached maximum
output the dampers are driven to the heating period's minimum limit.
When the temperature must be increased, the
dampers are driven to the minimum limit of the heating period and after
that the heating output is increased. The most commonly used cascade
control principle.
27
DAMPERS
HRU
HEATING
COOLING
FAN CONTROL
+/-
Control
symbol
Minimum limit
during heating
Vinkki !
Vinkki !
If the heating output need is greater than the available
maximum heating output (e.g., HRU defrost), the amount of
fresh air is decreased to ensure a sufficient heating output.
Reason:
Vinkki !
Vinkki !
For energy saving reasons, a smaller amount of fresh air is
used during heating.
Reason: