EH-105
DAMPERS
DAMPER SETTINGS
P-area
I-time
D-time
30 °C
80 s
0.0 s
5 ... 100 °C
10 ... 500 s
0.0 ... 5.0 s
DAMPER ACTUATOR SELECTION
DAMPER TUNING VALUES
Outdoor temperature at which the fresh air damper minimum position is linearly
changed toward the ”Damper max” limit.
Outdoor temperature at which the fresh air damper minimum limit drives the
damper to the maximum position.
Fresh air damper position during night heating.
Fresh air damper minimum position during cooling, if the outdoor air is warmer
that the room air or exhaust air (0% = damper is shut).
Pre-opening
DampStdMix
Min. posit.
Max. posit.
Min/CO2
Max/CO2
0
30%
30
100
600
1000
-15
+10
0%
30%
0 ... 100%
0...100%
0 ... 100%
0 ... 100%
500...1800ppm
700...2000ppm
-30 ...+30°C
-30 ...+30°C
0 ... 100%
0 … 100%
EH-105 dampers have PID control
Range:
Factory setting:
ADDITIONAL INFORMATION ABOUT SETTINGS:
Factory
setting:
Setting:
Range:
Explanation:
The minimum and maximum position of the damper can also be set in the user
level (see p. 9)
The minimum and maximum CO content can also be set in the user level
(see p. 10)
2
Damper
Operation mode
Settings
Tuning values
Actuator
Select
Mainten.mode
Damper
Select the damper actuator control mode and set the
drive time. The drive time means the time during
which the actuator drives the valve continuously
from a closed to an open position.
The range is 5…150s. The
character is at the
selected control mode.
34
Settings
Pre-opening
%
DampStdMix
%
Min.posit.
%
Max.posit.
%
Min/CO2
ppm
Max/CO2
ppm
Posit./OutdT->
N.HeatPosit
%
Min/Cooling
%
0
30
30
100
600
1000
0
30
Position/Outd.T
Min
/
°C
Max
/
°C
-15
+10
Tuningvalues
P-area
°C
I-time
s
D-time
s
30
80
0.0
Actuator
0
-10V/time
s
-10V/time
s
2
10-0V/time
s
24VAC On/Off51
90
0
90
9
The controller opens the dampers by the ”Pre-opening” amount before the controller
starts up the AH unit. Pre-opening also functions with On/Off controlled dampers,
with 100% equivalent to 100 seconds. The function prevents the air handling
channels from becoming damaged during start-up.
Constant position of the fresh air damper while the AH unit is running (100% =
damper open)
Fresh air damper minimum position (Can also be installed in the user level)
Fresh air damper maximum position (Can also be installed in the user level)
CO content at which the minimum limit position of the fresh air damper is linearly
changed toward the ”Damper max” limit.
CO content at which the fresh air damper minimum limit drives the damper to the
maximum position (see p. 33). Min/CO2 and Max/CO2 cannot be set closer than
200 ppm to each other (programmed locking). Attention. AH unit running and shut
down according to CO content see p. 29 and 31.
2
2
2
Settings Tuning values
Actuator selection
The minimum limit of the fresh air damper changes linearly
according to the outdoor temperature.
Posit./OutdT->
Min / -15°C
Max/ +10°C
N.HeatPosit
Min/Cooling
Instr.
p.23