background image

AHU temp. ctrl

Supply control
Room control
ExhaustControl
Outd T/Supp T

Supply control:
Room control:
ExhaustControl:

Outd T/Supp T:

.

t

blown in air (supply air) has a constant temperature.

the supply air temp. is controlled according to the room temp. (cascade control)

he supply air temperature is controlled according to the exhaust air temperature
(cascade control).

the supply air temperature is controlled according to the outdoor temperature.

EH-105

TEMPERATURE CONTROL

Operating mode

AHU fan control

AHU FAN CONTROL

AHU fan control

1/2 + 1/1speed
1/1 speed
AC freq.conv->

AC freq.conv.

Constant press
Min-max press
Constant speed
Min-max speed

AHU run indicat.

In use
Not in use

1/2 + 1/1 speed:

An air handling unit with contactor controlled 2-speed fans is in use. The

controller controls the fans by relay 1 (1/1output) and relay 2 (1/2 output). The supply air and
exhaust air fans run at the same time (locked in electrical control box).

The fan type and control mode are selected here.

1/1 speed:

An air handling unit with contactor controlled 1-speed fans is in use. The controller

controls both fans by relay 1 (locked in electrical control box).

AC freq.conv

An air handling unit whose fan rotation speed is controlled by an AC freq. converter

is in use. The controller uses a 0…10V control to control the fan speed. Supply fan control: strip
connector 65. Exhaust fan control: strip connector 66. The AC freq. converter running permit is
given to the supply air unit by relay 1 and to the exhaust air unit by relay 2.

Constant press:

Min-max press:

Constant speed:

Min-max spped:

AC freq. converters

AC freq. converters

AC freq. converter

AC freq. converter

The controller controls the fan rotation speed by

so that a constant pressure is maintained in the supply and

exhaust channels. Constant pressure settings are given in the maintenance mode (settings p. 30, AH max output/ SF pressure/ EF pressure). The
function requires channel pressure emitter measurements. AH max output = constant pressure in SF and EF channels. The pressure control uses SF
FanPDE/ EF FanPDE- measurements (constant air flow control), if SF press./EF press.-measurements are not connected.

The controller controls the fan rotation speed by

so that the supply and exhaust channel pressures correspond with

the desired output. (p. 30, AH max output/ SF and EF pressure, AH min output/ SF and EF pressure).
The pressure control uses SF FanPDE/ EF FanPDE- measurements (min-max air flow control), if SF press./EF press.-measurements are not connected.

The controller controls the fans to a constant rotation speed by

s. Settings are given in the maintenance mode (p. 30,

AH max output/ SF control/ EF control). AH max output = SF and EF fans run at a constant speed.

The controller controls the fan rotation speed by

s so that the desired AH output is realised. Settings are given in the

maintenance mode (p. 30, AH max output/ SF and EF control, AH min output/ SF and EF control).

AHU run indication: In use:

The running indication is connected to the controller. When the running indication "appears" to the controller from the AH unit, the

controller starts to regulate the control sequences from the stand-by situation to the "normal running (operation)" stage. The running indication is possible to connect
either to the digital input (see page 44) or to the strip connector 81 = 230 V running indication.

When the running indication is in use, it is also possible to take the

contradiction alarms in use.

The running indication from the AH unit is not connected. The AH unit can get started only by the controller. The controller regulates on “normal

running control”, when the controller gives to the AH unit min-or max output (1/1-or 1/2-output) control (the running indication is not connected). Otherwise
the control is on stand-by stage.

Not in use:

AHU controls
Operation mode
Settings
Tuning values
Actuator

Operating mode

AHU temp.ctrl
AHU fan control
AHU output ctrl

28

Hint !

Hint !

Press the group select button to

browse other operating modes that have
been selected.

AH CONTROLS

Operating mode

Select

Mainten.mode

AHU controls

C

C

With AH output control, air handling output limits can be taken into use based on the outdoor
temperature and cascade control, and air handling enhancement can be taken into use based on
CO2 content, room temperature or humidity.

AH OUTPUT CONTROL

Operating mode

AHU temp. ctrl
AHU fan control
AHU output ctrl

AHU output ctrl

Outdoor temp.
Cascade ctrl
CO2 content
Room temp.
Room humidity

OutdT/Output lim

Not in use
In use

In contactor controlled AH units

In AC freq. converter controlled AH units

, the fan output drops to ½ speed when the

outdoor temperature drops below the output exchange set value.

the AH unit output is steplessly

limited from maximum to minimum as the outdoor temperature drops from the
given AH maximum outdoor temperature to the given AH minimum outdoor
temperature (see p. 31). The outdoor temperature limit can always decrease air
handling regardless of other control commands.

Instr.

p.23

Содержание EH-105

Страница 1: ...of the year e g summer holidays sundays during the week etc Alarms can be received and acknowledged time programs and settings can be adjusted and measurement data can be read quickly via text messag...

Страница 2: ...Browse button moves the cursor up and down Group select button moves you from one control sequence to the next Dampers HRU Heating Cooling AH unit control Symbols for control Header text E g Sports ha...

Страница 3: ...ing Cooling 24VAC controls Text message connection via the bus Text message connection via GSM modem Maintenance NTC measurements Transmitter measurements B alarms Using the browser Measurements 5 12...

Страница 4: ...ler AH unit shut down Continuous control selected from the controller AH unit at max output Timer control selected from the controller AH unit at min output Timer control selected from the controller...

Страница 5: ...Ret Wat Exh aft HRU SuppAfterHRU RemoteSetPot FreeMeasurem 50 50 C 30 100 C 30 100 C 30 100 C 30 100 C 30 100 C 30 100 C 30 100 C 30 100 C Transmitter measurements strip connectors 7 11 The setting r...

Страница 6: ...s shorter than the old name the extra characters are replaced with an empty character If the new name is longer the text editor will give the letter that has been fed last as the new letter The charac...

Страница 7: ...sent when a STOP command is set from the controller STOP maintenance also stops control from the running permit relay R3 MIN timer h MAX timer h 0 00 0 00 In this mode the air handling unit control m...

Страница 8: ...controller is at or when a STOP command comes from the bus An also shuts down the AH unit The AH unit is shut down by relays 1 and 2 Emergency STOP Maintenance STOP A alarm as well as running permit...

Страница 9: ...h has been shut down starts up at full output and the dampers go to the night heating position see p 34 N HeatPosit When the room temperature rises by the amount of the hysteresis the controller shuts...

Страница 10: ...output maximum output when the CO content rises to the CO Maximum value given here The controller switches the AH unit output to minimum output when the CO content has been 200 ppm below the CO Maximu...

Страница 11: ...or Room temperature setting during night heating or Supply temperature setting or Temperature setting when the temperature control switch is turned off This is another setting for the room exhaust or...

Страница 12: ...utlined in the operating instructions on pages 44 45 12 Connection info 1 Outdoor temp 2 Supply temp 3 Exhaust temp 4 Return water 5 SupplyAft HRU 6 7 HRU frostPDE 8 SF press 9 EF press 10 SF filterPD...

Страница 13: ...ally or manually operated either mechanically or electrically Each control sequence has factory set automatic control AHU 1 1 Autom Room temp 21 2 SupplyTemp20 4 Selection M M C C OPERATING INSTRUCTIO...

Страница 14: ...n the special calendar for a certain day of the year A week program An extra eighth day program With the a normal calendar weekday can be changed to some other weekday It is also possible to give a co...

Страница 15: ...program Reply message 1 Reply message 2 There is a max of 5 connecting moments in one reply message When a week day is changed the AH unit runs at the normal starting situation output of the changed...

Страница 16: ...e AH unit Supply or exhaust air temperature is above the Fire risk value see p 24 The controller shuts down the AH unit AH unit heating s circulating pump s temperature relay alarm The controller shut...

Страница 17: ...breaks When the controller has given a fan speed running command and does not receive running information for 35 s the controller gives a contradiction alarm SF running info EF running info SF runnin...

Страница 18: ...en the GSM sends the same message back to the controller If the alarm is not acknowledged by GSM 1 within 5 min the controller sends the text message again to both GSM numbers Before acknowledging an...

Страница 19: ...the adjoining picture Press ESC OK Press the button to move cursor to Language kieli Press OK Language kieli Suomi English Svenska P cc Estonian Press the button to move the cursor to the language yo...

Страница 20: ...AHU output info Connection info ControlOperMode Clock functions Alarms Language kieli Type info Initializ modem Mainten mode AHU 1 1 Autom Room temp 21 2 SupplyTemp20 4 Selection C C OPERATION CODE o1...

Страница 21: ...m Room temp 21 2 SupplyTemp20 4 Selection C C Initializ modem appears on the menu only if the modem has been taken into use stripconnector B D pins are connected Press to send initializing commands to...

Страница 22: ...1 immediately receives the alarm information If the alarm is not acknowledged the controller sends a new text message to both GSM numbers 5 minutes after the alarm has appeared AHU control SETTINGS S...

Страница 23: ...factory settings locking the controller s user menu LON settings initializing bus measurements as well as modem settings and text message settings Press until the display no longer changes You are th...

Страница 24: ...ng risk set value of 4 C The cut off point during a trial run is above the set value of 20 C The number of degrees that StartIncrease raises the controller determined supply air temperature during the...

Страница 25: ...perature when raising the room temperature The recommended setting for displacement air handling is approx 2 C If the supply air does not fall to floor level in an air heated room lower this setting a...

Страница 26: ...temperature is higher than the set cooling inhibit set value and 2 The room temperature is higher than the room temperature setting by the amount of the heating cooling hysteresis and 3 The heating ou...

Страница 27: ...s reached maximum output the dampers are driven to the heating period s minimum limit When the temperature must be increased the dampers are driven to the minimum limit of the heating period and after...

Страница 28: ...DE EF FanPDE measurements min max air flow control if SF press EF press measurements are not connected The controller controls the fans to a constant rotation speed by s Settings are given in the main...

Страница 29: ...OutpLim cascade control can be used in AC freq converter controlled AH units The function is not in use during heaing when the HeatBoost setting is at 0 The function is not in use during cooling when...

Страница 30: ...Supply air unit channel pressure setting or SF FanPDE Attention Setting the SF control too high may limit realization of channel pressure Control by exhaust air fans s AC freq converter 0 10V control...

Страница 31: ...converter controlled AH unit output A maximum output is reached when the room temperature deviates from the set value by the HeatBoost set value 1 C In contactor controlled AH units the controller dr...

Страница 32: ...tion alarms for SF and EF fans Select Mainten mode Actuator alarm Select Mainten mode AHU stop alarm Instr p 23 AHU start after alarm is deactiv Contr acknowl Also remoteAck Alarm selections are made...

Страница 33: ...ition of constant position dampers can only be driven by a voltage controlled actuator ppm Fresh air damper minimum position 600 1000 30 100 Summer function reverse With the reverse summer function th...

Страница 34: ...ange is 5 150s The character is at the selected control mode 34 Settings Pre opening DampStdMix Min posit Max posit Min CO2 ppm Max CO2 ppm Posit OutdT N HeatPosit Min Cooling 0 30 30 100 600 1000 0 3...

Страница 35: ...d in the HRU which is driven to a higher output when the temperature needs to be increased HRU has a reverse summer function When it is warmer outside than inside and when half of the hysteresis betwe...

Страница 36: ...en the outdoor temperature is above 7 C Control of HRU output when the AH unit is shut down set the cube HRU at 100 and other HRU s at 0 Attention Cleaning function At the 0 setting the controller dri...

Страница 37: ...ection function is not in use Factory setting Setting Range Explanation Heating Operation mode Settings Tuning values Actuator Operating mode Radiator ElectricHeater Not in use PostVentilat if alarm s...

Страница 38: ...ype control magnetic valves or continuous control glycol cooling can be used with mechanical cooling The cooling unit running permit can be obtained from strip connectors 42 43 or 51 activated in actu...

Страница 39: ...inimum limit PI control is set with P min limit and I min limit settings When the supply air temperature drops below the set minimum value the supply air temperature minimum limit s PI controller begi...

Страница 40: ...tions as follows When the supply air temperature exceeds the supply air temperature set value and the set reverse delay time has passed the PI controller begins increasing the actuator control When th...

Страница 41: ...t be higher than the cooling set value and actuator control is above 2 Attention The cooling unit running permit is deleted if actuator control of cooling has been at 0 for 20 min Glycol cooling pump...

Страница 42: ...asurement channels 1 6 can also be used for receiving On Off information Taking On Off information into use see p 44 Use of NTC measurement channel for receiving On Off inputs Meas 3 Meas 4 Meas 5 Mea...

Страница 43: ...s time constant CO2 content of air Room air humidity percentage or remote setting potentiom transmitter 0 10V Supply air flow speed used for flow detector function Exhaust air flow speed used for flow...

Страница 44: ...UTO Switch Emerg Stop S SF 1 2 run EF 1 1 run EF 1 2 run SF fConvOver EF fConvOver SF fan PDS EF fan PDS Pumprun Pump run Pump run SF 1 1TRela SF 1 2TRela F 1 1TRela EF 1 2TRela Pump T Rela Pump T Rel...

Страница 45: ...ing information on off input or strip conn 81 is received A contradiction alarm is also given by the Actuator alarm AH fans ContradicAlrm selection if running information has not been received and the...

Страница 46: ...lly heated AH units do not have post ventilation In the event of an alarm the dampers remain in the selected position Pump T Rela Contact information from the HRU pump s temperature relay When the con...

Страница 47: ...de OK OK ESC Clears the alarm buffers and alarm history The operation code includes the following information about controller settings Attention When settings are restored the items included in the f...

Страница 48: ...m Move the cursor to the measurement you want and press If you want to select a series traffic bus for the measurement in question move the cursor to Bus and press The character indicates that the mea...

Страница 49: ...nitialized from the controller LON initializ No Yes Service switch LON ne t 78kbps A C EH 485 adapter card LON 100 adapter card Eg Datajamak 2x 2 1 x0 24 A B C RS 485 net EH 105 EH 105 Modbus net MODB...

Страница 50: ...ing the EH 485 bus adapter card and a modem can be connected to the RS 485 field bus through the master device EH 686 An EH 485 bus adapter card must be installed in the controller so that the EH 105...

Страница 51: ...ssage center number with or button Confirm by pressing Give the SIM card s PIN code The regulator will not initialize the GSM modem before the PIN code is installed The SIM card has to be put in the G...

Страница 52: ...n the EH net and the network By using the browser it is possible to communicate with the EH 105 controller from any pc Information from the controller can be read and changed from the pc If desired en...

Страница 53: ...pull the cover out of place Detach the keyboard display unit carefully by prying it with a screwdriver Turn the keyboard display unit into the opposite position Press the keyboard display unit carefu...

Страница 54: ...0VAC SF AC f converter control 0 10V Cooling control 0 10V Damper control 0 10V HRU control 0 10V Heating control 0 10V 24VAC or damper On Off 24 VAC 24 VAC 51 64 Heating actuator 24 VAC 0 10VDC ctrl...

Страница 55: ...U efficiency measurement TMD SF channel exhaust air CO2 content room measurement CO 2 SF filter detector EF filter detector Heating pump running information Supply air unit running information Exhaust...

Страница 56: ...on from 1 1 output TMD TMI CONTACTOR CONTROLLED AH UNIT WITH CONTRADICTION ALARMS Room temperature Supply air after HRU HRU efficiency measurement TMR SF fan 1 1 running information PDS NET 24VAC or d...

Страница 57: ...rol Neutral wire 230 VAC AH unit running information 230V Control voltage Power supply 230 VAC 50Hz 230V Control voltage Dig 1 Dig 2 Dig 3 Relay 1 N L L 230V N 21 23 25 41 Relay 2 Relay 3 24 VAC 24 Di...

Страница 58: ...functions transfer alarms using digital inputs and make an individual regulating circuit EH 686 can also function as a master in the Ouman RS 485 bus by directing traffic in the bus MODBUS 100 MODBUS...

Страница 59: ...45 Running time counter 6 Sensor fault 5 16 18 Sequence delay 24 Settings user level 9 Settings maintenance level 24 30 32 34 36 37 SF Ac Freq Converter override 8 45 Smoke alarm 46 Special calendar...

Страница 60: ...ces 1 running information 6 pieces 0 10 or 2 10 VDC 1 24VAC DC 1A 2 pieces 230VAC 6 1 A or 24VAC DC 6 1 A resistive load 6A inductive load 1A 1 230VAC 6 1 A 230 VAC control inputs Ouman Oy www ouman f...

Отзывы: