KEYWORD:
Settings
EH-105
Ajan asetus
5.0...45.0°C
-50...50°C
0...100%
0...100%
0...100%
0...100%
14°C
30%
30%
-15°C
100%
30%
Outdoor sensor must be con-
nected. The hysteresis is 2°C
Outdoor temperature at which the AH unit 1/1
output changes to ½ output.
SuppMinCool
OutputChange
Damper min
%
DampMinCool
%
Damper max
%
DampStdMix
%
Minimum position for fresh air damper during
heating (0% = damper closed)
Minimum position for fresh air damper during
cooling (0% = damper closed)
Maximum position for fresh air damper
(100% = damper open)
Constant position for the fresh air damper when
the AH unit is running (100% = damper open)
Can be seen if the dampers
operate by cascade control (see
damper operation p. 33)
Can be seen if the dampers
operate by constant position
(see p. 33).
The controller has an AH unit running time counter. Enter the counter's alarm limit
at which the controller requests maintainance of the AH unit. The alarm is shut off
by raising the maintenance limit or by resetting the AH unit counter (see p. 6). If
the setting is ”0”, the maintenance alarm is not in use.
AHUoutput/CO2 ppm
Minimum /
600
Maximum /
1000
CO2PostRun 15min
Damper / CO2 ppm
Minimum /
600
Maksimum/
1000
600ppm
500...1800
Damper position at
different
CO contents
2
ppm
CO2PostRun
10
100
80
60
40
20
0
%
500 600 700 800 900 1000
0 ... 99 min
The controller starts up the AH unit to ½ or minimum output when the CO
content rises 100 ppm above the CO "Minimum" value given here. The controller
shuts down the AH unit when the CO content has been below the CO "Minimum"
value for the post-running time.
The controller switches the AH unit to 1/1 output (maximum output),when the CO
content rises to the CO "Maximum" value given here. The controller switches the
AH unit output to ½ (minimum output), when the CO content has been 200 ppm
below the CO "Maximum" value for the post-running time.
Attention! AC inverter AH units: stepless AH unit control according to the CO
content.
2
2
2
2
2
2
2
2
2
15 min
Attention!
Additional information about settings
Settings for dampers:
Controller maintenance reminder setting:
Settings for controls according to CO2 content:
600ppm
500...1800
1000ppm 700...2000
AH unit start-up according to the CO2 content (see p. 31):
1000ppm 700...2000
Supply air minimum temperature when the
outdoor temperature is above the ”Outd.inhibit”
limit and ½ of the ”Heat/CoolHys” setting has
been realized. See pages 39.
Text on the
display:
Factory
settings:
Setting
range:
Explanation:
MaintInter
6000h
0...9900h
Damper control according to CO2 content. (see p. 33):
The dampers begin to open from the "Damper min. "
position when the CO content has risen above the
CO "Minimum" value.
The dampers open to the "Damper max." position
when the CO content has risen above the CO
"Maximum" value.
2
2
2
2
AH unit post-running time:
When the CO content control switches the AH unit
from maximum control to minimum control or shuts down the AH unit from
minimum control, the change occurs after the CO post-running time. This
prevents the AH unit from switching too soon from one operating mode to the next
when the CO content changes quickly.
2
2
2
SETTINGS:
...continuing ...
Damper max
%/
MaintInter
h/
AHUoutput:CO2ppm
(Minimum 600/Maximum
1000(CO2PostRun15min)
Damper ppm (Minimum
600/Maximum 1000)
100
6000
SETTINGS:
Room temp.
Supply temp
/
/
Temp.2
/
SuppMinCool
/
Room temp N
/
OutputChange
/
Damper min
%/
DampMinCool
%/
... Continuing...
21.5
21.5
23.5
13
16.0
-15
30
30