Alarm central
Relay 1
N
L
L (230V)
N
11
21
23
25
41
Relay 2
Relay 3
24 VAC
24
71
72
73
74
42
41
HRU
Heating
Cooling
EF unit
76
81
82
83
Damper
SF unit
22
26
31
24 VAC
65
Running
information 230 V
Cooling control 0 ... 10V
Damper control 0 ... 10V
HRU control 0 ... 10V
Heating control 0 ... 10V
24 VAC output
24 VAC output
51
64
63
61
43
32
62
66
75
27
2 x 0.8 KLMA
2 x 0.8 KLMA
4 x 1.5 N
Supply air unit running permit to AC f. converter
Exhaust air unit running permit to AC f. converter
Neutral wire
230 VAC, 50Hz
Power supply
Control voltage 230V
AC FREQ. CONVERTER CONTROLLED AHU WITH CONTRADICTION ALARMS
TMO tai TMD
EIA-232 RX
EIA-232 TX
EIA-232 GND
2 x 0.8
DATAJAMAK
2x(2+1)x0,24
Field device
1
2 x 0.8
2 x 0.8
2
3
TMW tai TMS
TMD
4
5
6
TMD
2 x 0.8
2 x 0.8
2 x 0.8
TMW tai TMS
7
8
9
4 x 0.8
4 x 0.8
4 x 0.8
10
4 x 0.8
A
B
C
D
Pressure difference transmitter above the HRU
(frosting over information)
TMD
TMI
Outdoor temperature
Exhaust air temperature
Supply air temperature B
Supply air after HRU
(HRU efficiency measurement)
TMD
SF channel (exhaust air)
CO2 -content (room measurement)
CO 2
SF filter detector
EF filter detector
Heating pump running information
Supply air unit running information
Exhaust air unit running information
Alarm information from the cooling unit
SF channel pressure (supply air)
PDE
PDE
PDE
EH-105
CONNECTION GUIDE
example 1
EH-105
NET
On/Off-damper actuator control
24 VAC
Control on cooling's running permit relay
24 VAC
24 VAC
24 VAC
55
42
42
42
42
AH running permit for distribution center (230VAC, 6(1)A)
Meas.3
Meas.4
Meas.5
Meas.6
Meas.7
Meas.8
Meas.9
Meas.10
Meas.11
Dig 1
Dig 2
Dig 3
Bus
Interface
Meas.1
Meas.2
Dig 4
Dig 5
Dig 6
Dig 7
Alarm
Contact
Supply air temperature
Radiator circuit return water temperature
(Electric heater overheating protection)
Alarm information from controller
max. 46 V, 1A
Heating actuator
24 VAC
0...10VDC-ctrl
63
41
Damper On/Off 24VAC
One wire control
24VAC
51
41
Open
EF AC f. converter control 0 ... 10V
SF AC f. converter control 0 ... 10V
Gr
Ye
AB
C
D
Jumper
wire
Modem connection
Br
Modem
connecting
cable
If the modem is connected to the RS-485 bus, see Connection
in the instructions that come with the RS-485 card.
EH-105
regulator