PRODUCT SETTINGS AND CONFIGURATION
27
OI-6000K-X-X-X-NXP-X OPS_GUIDE_REV 1.0
If the fault terminal cannot be used, Otis Instruments recommends one of the following configurations:
Recommended Configurations for Relay Fail-Safe Setting
Power Source
Relay Wiring
Fail-Safe Outcome
OI-6000K
Normally-Closed (NC) No (Off) Normal Operation: Closed
Alarm Activation: Open
OI-6000K
Normally-Open (NO)
Yes (On) Normal Operation: Closed
Alarm Activation: Open
External Power Supply Normally-Closed (NC) Yes (On) Normal Operation: Open
Alarm Activation: Closed
External Power Supply Normally-Open (NO)
Yes (On) Normal Operation: Closed
Alarm Activation: Closed
3.6.1
RELAY 1: FAIL-SAFE SETTING
1.
Use the
ADD
and
SUB
buttons to select the desired fail-safe setting
for Relay 1. Select “Yes”
to turn the fail-safe setting on, or
select “No” to leave the fail
-safe setting off.
2.
Press the
MENU
button to select the desired setting and to advance to the Relay 2 fail-safe
setting screen.
3.6.2
RELAY 2: FAIL-SAFE SETTING
1.
Use the
ADD
and
SUB
buttons to select the desired fail-safe setting
for Relay 2. Select “Yes”
to turn the fail-safe setting on,
or select “No” to leave the fail
-safe setting off.
2.
Press the
MENU
button to select the desired setting and to advance to the Fault Terminal Fail-
Safe setting screen.