The MRLDS-450 refrigerant gas detector is designed for use in refrigeration 
applications and may be used as a stand-alone device, or connected to a facility’s 
building management system (BMS). It enables compliance with refrigerant 
safety codes (ASHRAE 15 and EN378) and features audible and visual alarms to 
alert personnel in the event of a refrigerant leak. 

1. Safety Instructions

DANGER: 

The MRLDS-450 is NOT certified or approved for operation in 

 oxygen-enriched atmospheres. Failure to comply may result in severe injury or 
death.

WARNING: 

Use this product ONLY for the purposes and under the conditions 

listed in the user manual. Failure to comply may result in injury and/or damage 
to the product. The MRLDS-450 has not been designed to be intrinsically safe 
for use in areas classified as being hazardous locations. For your safety, DO NOT use in 
hazardous locations. Consult a qualified professional before connecting the MRLDS-450 to devices not mentioned in 
this manual. Failure to comply may result in injury and/or damage to the product.

WARNING: 

The gas diffusion path can become occluded (moisture, dust, debris, frozen condensation) over time, resulting in 

reduced or complete lack of gas detection and alarming function. Routine visual inspection of the gas detector and bump 
testing are recommended to ensure proper gas detection and alarm function. For information on calibrating the sensor, refer to 
the Care and Maintenance section of the MRLDS-450 User Manual P/N 026-1316.

CAUTION: 

Except for the maintenance detailed in this manual, this product should ONLY be opened and/or 

serviced by authorized personnel. Failure to comply may void the warranty.

CODE COMPLIANCE:

 Comply with all local and national laws, rules and regulations associated with this equipment. Operators 

should be aware of the regulations and standards in their industry/locality for the operation of the MRLDS-450.

TECHNICIAN USE ONLY: 

The MRLDS-450 must be installed by a suitably qualified technician who will install this unit in 

accordance with these instructions and the standards in their particular industry/locality. This document is only intended as a 
guide and the manufacturer bears no responsibility for the installation or operation of this unit. Failure to install and operate the 
unit in accordance with these instructions and with industry guidelines may cause serious injury or death and the manufacturer 
will not be held responsible in this regard.

Figure 1 - Refrigerant Gas Detector

Quick Start Guide

Refrigerant Gas Detector (MRLDS-450)
for Machinery Rooms, Cold Rooms and Freezers 

Summary of Contents for MRLDS-450

Page 1: ...n become occluded moisture dust debris frozen condensation over time resulting in reduced or complete lack of gas detection and alarming function Routine visual inspection of the gas detector and bump...

Page 2: ...mponent Description 1 M16 Cable Glands x6 2 Rubber Gasket 3 Internal Alarm Buzzer 4 Power Connections x2 5 Digital Connection Modbus 6 Analog Connection 7 Tactile Switch 1 8 Ribbon Cable Connection To...

Page 3: ...3 9 10 cm Alarm Delay Configurable 0 to 15 minutes Inputs Tactile Switches x2 Magnetic Switches x2 Outputs Analog Output 1 to 5V default 0 to 5V 0 to 10V 2 to10V or 4 to 20mA Bluetooth Bluetooth Low...

Page 4: ...ANT Cable glands are meant to accommodate one cable DO NOT use cable glands for more than one cable IMPORTANT If analog output is 4 to 20mA connect or short the connection to ensure the gas detector d...

Page 5: ...an X tightening pattern 5 MRLDS 450 Network Setup for Site Supervisor and E2 For Modbus end of line termination use 150 ohm resistor or termination block P N 537 2711 Do not use MRLDS 120 ohm on boar...

Page 6: ...Emerson Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emerson com for the latest technical documentation and updates 5a Site Supervisor Device a...

Page 7: ...ions Inc This document may be photocopied for personal use Visit our website at http www emerson com for the latest technical documentation and updates 5b E2 Device and COMM Setup Figure 8 E2 Setup Fo...

Page 8: ...0 App and click the Bluetooth icon at the bottom of the screen to initiate a scan 3 Select the instrument default is 18TMAE from the list of available gas detectors 4 When prompted enter the passkey d...

Page 9: ...S setup of E2 please see the Quick Setup Guide P N 026 4419 For Technical Support call 770 425 2724 or email ColdChain TechnicalServices Emerson com Emerson P N IP66 3 x Relays Analog Output Modbus Ou...

Reviews: