INSTALLATION AND STARTUP
17
OI-6000K-X-X-X-NXP-X OPS_GUIDE_REV 1.0
2.3.5.3
CONNECTING OI-481-RGA STROBE LIGHT AND OI-488 HORN
–
O
2
SENSORS
On the OI-6000K Detector:
1.
Locate the wiring terminal block on the backplane of the enclosure and complete the
following:
a.
Connect a RED jumper wire to the positive supply terminal.
b.
Connect the BLACK wire from the OI-481-RGA to the negative supply terminal.
c.
Connect the BLACK wire from the OI-488 to the negative supply terminal as well.
2.
Locate the Relay 1 terminal block on the radio/relay board and complete the following:
a.
Conn
ect a BLUE jumper wire to the “COM” terminal.
b.
Connect the YELLOW wire from the OI-481-RGA
to the “NO” terminal.
c.
Connect the GREEN & BLUE wire from the OI-481-RGA
to the “NC” terminal.
3.
Locate the Relay 2 terminal block on the radio/relay board and complete the following:
a.
Connect the RED jumper to the “COM” terminal.
b.
Connect the BLUE jumper to the “
NC
”
terminal.
c.
Connect the RED wire from the OI-481-
X to the “NO” t
erminal.
d.
Connect the RED wire from the OI-
488 to the “NO”
terminal as well.
Содержание OI-6000K NXP Series
Страница 1: ......
Страница 2: ......
Страница 67: ...APPENDICES OI 6000K X X X NXP X OPS_GUIDE_REV 1 0 62 Notes ...