IG-183-EN version 06; 31/03/2020
75
General instructions
cgm
.3 system: medium voltage SF
6
gas-insulated
cubicles up to 38 kV according to IEEE and CSA standards
Safety elements
6. Safety elements
6.1. Earthing prevention acoustic alarm unit
The
ekor
.sas earthing prevention alarm is an acoustic
indicator which works in association with the earthing shaft
lever and the
ekor
.vpis voltage presence indicator. Both
thus operate within the same range.
The alarm is activated when there is voltage in the cubicle’s
MV feeder and the lever is inserted in the earthing switch
shaft. A sound then warns the operator that if he performs
the operation, a short-circuit in the network might occur.
Optional
unit supplied on demand. Incompatible with
ekor
.ivds units.
6.2. Interlocks
The
cgm
.3 switchgear incorporates safety locks required to
ensure the following conditions:
1.
The switch-disconnector and the grounding switch
cannot both be in closed position at the same time.
2.
The cubicles have a safety lock which prevents access
to the medium voltage cable compartment while the
grounding switch is not closed. In normal operation,
this grounding switch cannot be opened if the cable
compartment cover is not in place.