IG-183-EN version 06; 31/03/2020
32
Installation
General instructions
cgm
.3 system: medium voltage SF
6
gas-insulated
cubicles up to 38 kV according to IEEE and CSA standards
2.
Remove the cable compartment cover, using the
central handle on the cover to pull it up and forward as
indicated in the figure.
Figure 4.11.
Removing the cable compartment cover
3.
Anchor the first medium voltage cubicle to the floor of
the installation, using screws at the points prepared in
its base. This will prevent vibrations or movements due
to short-circuits, possible flooding of the installation,
etc. Bear the following dimensions and figures in mind.
Figure 4.12.
Anchoring points in
cgm
.3
cubicles