MAINTENANCE
39 / 56
X700-3000_usermanual_engl_20170405.docx
CAUTION
A small arc can occur when the batteries are connected to the
UPS system. This is normal and represents no risk to person-
nel. Insert the battery cable quickly and firmly into the battery
plug connection in the UPS system.
7. Continue with Chapter 6.6
Testing the new batteries
.
6.6 Testing the new batteries
1. To charge the batteries, connect the UPS to the supply network
for 48 hours.
2. In normal mode, hold the ON /
/
button for at least 2 sec-
onds to start the self-test.
3. If the batteries are faulty, a warning is displayed automatically
(see Table 10: Warnings). Press “OK” to acknowledge a suc-
cessful battery test and to switch the UPS system back into nor-
mal mode.
PLEASE NOTE
The UPS system only starts a self-test when the batteries are
fully charged and the UPS system is in normal mode with no
active warning messages.
6.7 Disposing of the old batteries or UPS system
Find out from a local recycling centre how the old batteries or the UPS
system should properly be disposed of. Old batteries can also be re-
turned to ONLINE for disposal free of charge. Please contact Support
(see Chap. 7.5)
CAUTION
Batteries must not be burnt. There is risk of explosion.
Batteries must be disposed of properly. Find out about the lo-
cal disposal regulations.