OPERATION
20 / 56
X700-3000_usermanual_engl_20170405.docx
Symbol
Description
Function
Output sockets
Active UPS output
Battery
Battery symbol in DC link: UPS system in bat-
tery mode
Battery charging
Battery symbol in DC link: Battery in charging
mode
Bypass mode
Bypass mode, the load is supplied directly by
the supply network without UPS protection
High-efficiency
mode
The UPS system is working in high-efficiency
mode
CVCF
Frequency con-
verters
The UPS system is working in frequency con-
verter mode
PFC
Power factor cor-
rection
The power factor correction of the UPS sys-
tem is active
Table 3: Display
Alarm
Description
Every 10 seconds
UPS system in bypass mode
Every 5 seconds
UPS system in battery mode
Every 2 seconds
Battery voltage low
Every second
Overload
Continuous tone
Error
Table 4: Acoustic alarm
Abbrevia-
tion
Display
Description
AAT
Time in battery mode
AC
Active Closed
AO
Active Open
BF
Battery Fault
BL
Battery Low
BP
Batterypack