OPERATION
23 / 56
X700-3000_usermanual_engl_20170405.docx
Bypass mode:
If the UPS system is switched off, it is
switched to bypass instead of standby
mode.
[ENA] = Enabled
[DIS] = Disabled
“DIS”
Battery deep discharge protection:
Shutdown of all output sockets after time
defined here.
[0 – 999] = Shutdown after 0 to 999 sec-
onds.
[DIS] = Shutdown time dependent on bat-
tery capacity.
Attention: If the setting is [0], shutdown is
after 10 seconds.
“DIS”
Number of additional battery packs:
Selection of correct number of additional
battery packs
“0”
Autonomy time
Select from display
[AAT] = Remaining autonomy time
[RAT] = Time in battery mode
Emergency power off function:
[AO] = active open, emergency power off
is active with emergency power off con-
tact open
[AC] = active close, emergency power off
is active with emergency power off con-
tact closed
“AO”
External isolating transformer:
If the function is activated, the switch from
standby to UPS normal mode has a 90
degree phase shift and reduce the mag-
netisation current on the isolating trans-
former. If this function is disabled, the
switch is in phase zero crossing.
[ENA] = External isolating transformer al-
lowed on UPS output
[DIS] = External isolating transformer not
allowed on UPS output
“DIS”
Programmable output sockets:
[ENA] = Enabled
[DIS] = Disabled
“DIS”