COMMUNICATION AND INTERFACES
29 / 56
X700-3000_usermanual_engl_20170405.docx
5.2 Slot for interface cards
The XANTO features a slot (see Chap. 8.6
Rear view
) for the following
interface cards:
Product no.
Description
DW7SNMP30
SNMP adapter Basic
The SNMP adapter communicates via TCIP/IP with the load at-
tached to the network.
DW5SNMP30
SNMP adapter Professional
Works like
Basic
, but with additional interface for temperature sen-
sor and environment management.
DWAS400DC
AS400 relay card
Combined slot card for optional communication with IBM AS400
servers or individual use of relay contacts. The following mes-
sages/contact outputs are available: Normal mode, standby mode,
battery mode, battery voltage low, bypass mode, collective error,
input for UPS shutdown.
Table 8: Interface cards
PLEASE NOTE
The interface cards installed in the slot can be used in parallel
with the RS-232 or USB communication.
5.3 Emergency Power Off (EPO) function
The Emergency Power Off (EPO) function is used to remotely shut
down the UPS system and connected loads immediately. This means
removing the bridge on the emergency power off connector (back of
UPS system, see Fig. 15) and connecting an external emergency
power off switch.
Cross section of connecting cable = 0.5 - 2.5mm
2
(AWG 13 - 20)
Recommended cross-section of connecting cable = 1.5mm
2
(AWG 15)