O P E R A T I O N
87 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
Automatic bypass
"Enabled", "Disabled"
Recommendation: Do not change.
"Enabled"
Short circuit <4s
no alarm
"Enabled", "Disabled"
In the event of a short circuit <4s on the out-
put, no warning messages are generated for
"Enabled".
Recommendation: Do not change.
"Disabled"
Bypass voltage
low limit
120V, …. 215V
Recommendation: Do not change.
184V
Bypass voltage
high limit
245V, …. 276V
Recommendation: Do not change.
264V
Bypass frequency
low limit
-
1%, …. – 20%
Recommendation: Do not change.
- 10%
Bypass frequency
high limit
+ 1%, …. + 40%
Recommendation: Do not change.
+ 10%
HE voltage low
limit
-
5%, …. – 10%
Recommendation: Do not change.
- 5%
HE voltage high
limit
+
5%, …. + 10%
Recommendation: Do not change.
+ 5%
HE frequency low
limit
-
1%, …. – 10%
Recommendation: Do not change.
- 5%
HE frequency high
limit
+ 1%, …. + 10%
Recommendation: Do not change.
+ 5%
External battery
modules
0, 1, 2
Recommendation: Adapt to requirements.
0
Running time input
Days, hours, minutes and seconds
Running time can be adapted.
Recommendation: Do not change.
LCD contrast
-5, -
4, …. +4, +5
Recommendation: Adapt to requirements.
+0
Table 7: Settings menu
Содержание 10000 3/1 XANTO S Series
Страница 2: ...2 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 64: ...64 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 66: ...66 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 126: ...T E C H N I C A L D A T A 126 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler 9 3 CE conformity ...
Страница 128: ...128 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 130: ...130 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 190: ...D A T I T E C N I C I 190 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler 9 3 Dichiarazione CE ...
Страница 192: ...192 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...