I N S T A L L A T I O N
78 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
3.5.3
Connecting the external battery modules
NOTE
A maximum of two battery modules may be connected.
CAUTION
Batteries can pose an electric shock risk or catch fire due to
high short-circuit currents. Therefore the procedure for con-
necting the external battery module must be strictly complied
with.
1. Open the fuses on the battery modules (see Figure 7)
Figure 7: Opening the fuses on the battery module
2. Connect the terminal strip of the first external battery module
with the terminal strip of the UPS system using the supplied bat-
tery cable. Connect the second external battery pack with the
first external battery pack.
3. Reconnect the fuses to the battery modules.
4. Proceed with section "
Connecting the internal battery modules "
.
Содержание 10000 3/1 XANTO S Series