M A I N T E N A N C E
114 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
7.6
Testing the new batteries
1. Press the
button for at least one second to enable the menu
options. Select "CONTROL" and then "BATTERY TEST".
2.
Select “YES” and press the
button for at least one second
to start the battery test.
NOTE
Battery test requirements:
UPS system in normal state, no warning message
Bypass voltage acceptable
Load greater than 10%
The battery test (LEDs light up consecutively) takes ten seconds.
The display shows "STATUS: BATTERY TEST PROGRESSING". At
a positive result the display shows "STATUS: BATTERY TEST
PASSED".
7.7
Disposing of old batteries or the UPS system
Contact the recycling centre onsite or a special waste facility for in-
formation on disposing of the old batteries or UPS system properly.
You can also dispose of old batteries at ONLINE at no cost. Please
contact support for this option (see
Support
).
CAUTION
Batteries may not be incinerated. There is a risk of explosion
Batteries must be disposed of properly. Inform yourself about
the local disposal regulations
Do not open or damage the batteries. The battery acid can
attack the eyes and skin as well as cause poisoning
Содержание 10000 3/1 XANTO S Series
Страница 2: ...2 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 64: ...64 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 66: ...66 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 126: ...T E C H N I C A L D A T A 126 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler 9 3 CE conformity ...
Страница 128: ...128 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 130: ...130 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 190: ...D A T I T E C N I C I 190 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler 9 3 Dichiarazione CE ...
Страница 192: ...192 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...